4 project planning, Project planning, Profibus communication – Lenze I/O system 1000 System Manual User Manual
Page 393
PROFIBUS communication
Project planning
l
393
EDSIO1000 EN 7.0
9.4
Project planning
The I/O system is configured via the master. The following work steps must be carried out:
ƒ
Import the GSE file (device description) of the I/O system into the project planning
tool.
– PROFIBUS bus coupler: LENZ0C3A.gse
– The description or linkage of the GSE file can be found in the project planning tool.
ƒ
Address nodes
– Every node at the PROFIBUS is identified by an address.
– Each address may only be assigned once in a bus system.
– Addresses between 1 ... 125 can be assigned.
– At the PROFIBUS bus coupler (slave), the address with the front DIP switch is
set(
¶ 39).
– At the master, the address is set during the configuration.
ƒ
Set the baud rate
– The baud rate is set in the configuration tool.
– The baud rate must correspond to the length of the bus cable.
ƒ
Parameterise slaves
)
Note!
The diagnostic function is only supported by I/O compound modules from HW
version 1B and by bus coupler modules from HW version 1A.
If a module in the system complies with an earlier HW version, the diagnostic
function is deactivated for all modules.