PROFIBUS communication

Project planning

9

l

393

EDSIO1000 EN 7.0

9.4

Project planning

The I/O system is configured via the master. The following work steps must be carried out:

ƒ

Import the GSE file (device description) of the I/O system into the project planning
tool.
– PROFIBUS bus coupler: LENZ0C3A.gse
– The description or linkage of the GSE file can be found in the project planning tool.

ƒ

Address nodes
– Every node at the PROFIBUS is identified by an address.
– Each address may only be assigned once in a bus system.
– Addresses between 1 ... 125 can be assigned.
– At the PROFIBUS bus coupler (slave), the address with the front DIP switch is

set(

39).

– At the master, the address is set during the configuration.

ƒ

Set the baud rate
– The baud rate is set in the configuration tool.
– The baud rate must correspond to the length of the bus cable.

ƒ

Parameterise slaves

)

Note!

The diagnostic function is only supported by I/O compound modules from HW
version 1B and by bus coupler modules from HW version 1A.
If a module in the system complies with an earlier HW version, the diagnostic
function is deactivated for all modules.