12 i/o compound modules - communication, 1 rs232 interface - epm-s640, 12 i/o compound modules − communication – Lenze I/O system 1000 System Manual User Manual
Page 219: Rs232 interface − epm−s640, Product description
Product description
I/O compound modules − communication
RS232 interface − EPM−S640
l
219
EDSIO1000 EN 7.0
3.12
I/O compound modules − communication
3.12.1
RS232 interface − EPM−S640
)
Note!
This module can only be actuated on a bus coupler module with HW version
1D or higher.
This module features an RS232 interface for access to field devices with an RS232 interface.
For access to devices with an RS232 interface, the protocol of the field device must be
implemented in the control in each case.
The following handling blocks are provided:
IPC / control
Programming via
Bus system
Handling block
Lenze Industrial PC
l
EL 1800−9800
l
CS 5800−9800
l
CPC 2800
PLC Designer V2
l
CAN
l
EtherCAT
l
PROFIBUS
Data reception:
L_IO1000_EPMS640/650_RS232/485Write
Data transmission:
L_IO1000_EPMS640/650_RS232/485Read
L−force Controller
3200 C
PLC Designer V3
,
Further information on the subject ...
ƒ
"Serial process interfacing with I/O compound modules", see appendix.
ƒ
"Parameterisation", see in the corresponding chapter for the fieldbuses.
ƒ
"Handling blocks", see documentation for the PLC Designer.
Features
ƒ
Serial RS232 interface (isolated towards the backplane bus)
ƒ
Logic states as voltage level
ƒ
Transmission speed 150 bps ... 115.2 kbps
ƒ
Data transfer up to a distance of 15 m
ƒ
Hardware handshake (RTS/CTS)
ƒ
Protocols
– ASCII
– STX/ETX
– 3964(R)
ƒ
Up to 250 frames (1024 bytes of receive or transmit buffer)
ƒ
Character delay time can be parameterised in ms grid
ƒ
Parameter setting via 17 bytes of parameter data
ƒ
Modem Signals Management DTR−DSR−DCD