beautypg.com

Devicenet communication, Parameter data – Lenze I/O system 1000 System Manual User Manual

Page 586

background image

DeviceNet communication

Parameterising the counter
One counter 32 bits, 24 V DC − EPM−S600

11

l

586

EDSIO1000 EN 7.0

Parameter data

Pos. in
string of
digits

Name

Description/value

Lenze

1

Diagnostics

A diagnostic alarm occurs if the same event triggers a further
process alarm during a process alarm processing.
Bits 5 ... 0: Reserved
Bit 6: diagnostic alarm (0 = inhibited; 1 = enabled)
Bit 7: Reserved

00

h

2

Input frequency
track A

Filters for instance serve to filter signal peaks in the case of an
unclean input signal.
2 (02

h

): 100 kHz

3 (03

h

): 60 kHz

4 (04

h

): 30 kHz

6 (06

h

): 10 kHz

7 (07

h

): 5 kHz

8 (08

h

): 2 kHz

9 (09

h

): 1 kHz

Other values are not permissible!

02

h

3

Input frequency
track B

02

h

4

Input frequency latch

02

h

5

Input frequency gate

02

h

6

Input frequency reset

00

h

7

Reserved

8

Alarm response

Setting activates process alarm
Bit 0: Proc. alarm HW gate open
Bit 1: Proc. alarm HW gate closed
Bit 2: Proc. alarm overflow
Bit 3: Proc. alarm underflow
Bit 4: Proc. alarm comparison value
Bit 5: Proc. alarm final value
Bit 6: Proc. alarm latch value
Bit 7: Reserved

80

h

9

Counter function

Bit 5 ... 0:

000000

b

= counting continuously

000001

b

= counting once, main counting direction forwards

000010

b

= counting once, main counting direction backwards

000100

b

= counting once, no main counting direction

001000

b

= counting periodically, main counting direction

forwards
010000

b

= counting periodically, main counting direction

backwards
100000

b

= counting periodically, no main counting direction

Bits 7 ... 6: Reserved

40

h

10

Comparator

Bit 2 ... 0: output switches (... if condition is met)

000

b

= never

001

b

= count value

³ comparison value

010

b

= count value

£ comparison value

100

b

= count value = comparison value

Bit 3: Invert counting direction track B

0 = no (do not invert)
1 = yes (invert)

Bits 6 ... 4: Reset

000

b

= deactivated

001

b

= HIGH level

011

b

= rising edge

101

b

= rising edge, once

Bit 7: Reserved

00

h