PROFINET communication

Time stamp parameterising

2 digital inputs with time stamp function − EPM−S207

12

l

693

EDSIO1000 EN 7.0

Parameter data

Data set

Name

Description/value

Lenze

No.

Byte

02

h

0

Length − process
image input data

Length of input data (backplane bus communication); the
values are specified by the system. Other values are not
permissible.

14

h

or 3C

h

(fix)

1

Length − process
image output data

Length of output data (backplane bus communication);
the values are specified by the system. Other values are
not permissible.

00

h

(fix)

01

h

0

Input delay DI 1

00

h

= 1

ms

02

h

= 3

ms

04

h

= 10

ms

07

h

= 86

ms

09

h

= 342

ms

0C

h

= 273

ms

Other values are not permissible.

02

h

1

Input delay DI 2

02

h

80

h

0

Edge 0−1 an DI x

Time stamp entry on rising edge
Bit 0: DI 1 (0: inhibit, 1 = enable)
Bit 1: DI 2 (0: inhibit, 1 = enable)
Bits 7 ... 2: Reserved

00

h

1

Edge 1−0 at DI x

Time stamp entry on falling edge
Bit 0: DI 1 (0: inhibit, 1 = enable)
Bit 1: DI 2 (0: inhibit, 1 = enable)
Bits 7 ... 2: Reserved

00

h

Diagnostic data

Using SFB 52, you can read out the diagnostic bytes which provide information about the
module. With SFB 52 you can also read out data set 1 which contains further information.

Data set 1 is structured as follows:

Data set 1, diagnostics

Byte

Bit 7 ... 0

0

0 (fixed)

1

Bits 3 ... 0: module class, 1111

b

: digital module

Bit 4: channel information available
Bits 7 ... 5: 0 (fixed)

2

0 (fixed)

3

0 (fixed)

4

Bits 6 ... 0: channel type, 70

h

: digital module

Bit 7: more channel types available (0: yes; 1: no)

5

Number of diagnostic bits output by the module per channel (here 00

h

)

6

Number of channels of a module (here 02

h

)

7 ... 15

0 (fixed)