PROFINET communication
Time stamp parameterising
2 digital inputs with time stamp function − EPM−S207
l
693
EDSIO1000 EN 7.0
Parameter data
Data set
Name
Description/value
Lenze
No.
Byte
02
h
0
Length − process
image input data
Length of input data (backplane bus communication); the
values are specified by the system. Other values are not
permissible.
14
h
or 3C
h
(fix)
1
Length − process
image output data
Length of output data (backplane bus communication);
the values are specified by the system. Other values are
not permissible.
00
h
(fix)
01
h
0
Input delay DI 1
00
h
= 1
ms
02
h
= 3
ms
04
h
= 10
ms
07
h
= 86
ms
09
h
= 342
ms
0C
h
= 273
ms
Other values are not permissible.
02
h
1
Input delay DI 2
02
h
80
h
0
Edge 0−1 an DI x
Time stamp entry on rising edge
Bit 0: DI 1 (0: inhibit, 1 = enable)
Bit 1: DI 2 (0: inhibit, 1 = enable)
Bits 7 ... 2: Reserved
00
h
1
Edge 1−0 at DI x
Time stamp entry on falling edge
Bit 0: DI 1 (0: inhibit, 1 = enable)
Bit 1: DI 2 (0: inhibit, 1 = enable)
Bits 7 ... 2: Reserved
00
h
Diagnostic data
Using SFB 52, you can read out the diagnostic bytes which provide information about the
module. With SFB 52 you can also read out data set 1 which contains further information.
Data set 1 is structured as follows:
Data set 1, diagnostics
Byte
Bit 7 ... 0
0
0 (fixed)
1
Bits 3 ... 0: module class, 1111
b
: digital module
Bit 4: channel information available
Bits 7 ... 5: 0 (fixed)
2
0 (fixed)
3
0 (fixed)
4
Bits 6 ... 0: channel type, 70
h
: digital module
Bit 7: more channel types available (0: yes; 1: no)
5
Number of diagnostic bits output by the module per channel (here 00
h
)
6
Number of channels of a module (here 02
h
)
7 ... 15
0 (fixed)