I/O compound modules − counter
One counter 32 bits, 5 V DC − EPM−S602
l
190
EDSIO1000 EN 7.0
Messages of the status LEDs RUN and MF
RUN
MF
Meaning
On
Off
Module status OK
Bus communication is OK
On
On
Module reports error
Bus communication is OK
Off
On
Module reports error
Bus communication not possible
Off
Off
Error in the bus supply voltage
Blinking
Blinking
Configuration error (
^ 249)
Terminals
Module terminals, spring terminals
1
View
Designation
Explanation
Terminal data
2
6
3
7
4
8
1
5
1
5
4
8
1
Digital input "A+"/"pulse"
Differential input for counting
signal or track A of an encoder for
single, double, or quadruple
evaluation
10 mm
0.08 ... 1.5 mm²
(AWG 28 ... 16)
2
DC 5 V for encoder supply
3
GND
4
Digital input "B+"/"direction"
Differential input for direction
signal or track B of an encoder
(can be inverted via
parameterisation)
5
Digital input "A−"/"pulse"
See 1
6
Differential input for reset "Z+"
7
Differential input for reset "Z−"
SLIO002
8
Digital input "B−"/"direction"
See 4
Technical data
EPM−S602: rated data
Module identifier
2242
dec
Current consumption/power loss
Current consumption from backplane bus
70 mA
Power loss
0.85 W
Digital inputs
Number of inputs
0
Cable length
shielded
100 m
Load voltage
Nominal value
DC 20.4 ... 28.8 V
Current consumption from load voltage
L+
20 mA (without load)