beautypg.com

Product description, Terminals, Technical data – Lenze I/O system 1000 System Manual User Manual

Page 190

background image

Product description

I/O compound modules − counter
One counter 32 bits, 5 V DC − EPM−S602

3

l

190

EDSIO1000 EN 7.0

Messages of the status LEDs RUN and MF

RUN

MF

Meaning

On

Off

Module status OK
Bus communication is OK

On

On

Module reports error
Bus communication is OK

Off

On

Module reports error
Bus communication not possible

Off

Off

Error in the bus supply voltage

Blinking

Blinking

Configuration error (

^ 249)

Terminals

Module terminals, spring terminals

1

View

Designation

Explanation

Terminal data

2

6

3

7

4

8

1

5

1

5

4

8

1

Digital input "A+"/"pulse"
Differential input for counting
signal or track A of an encoder for
single, double, or quadruple
evaluation

10 mm

0.08 ... 1.5 mm²

(AWG 28 ... 16)

2

DC 5 V for encoder supply

3

GND

4

Digital input "B+"/"direction"
Differential input for direction
signal or track B of an encoder
(can be inverted via
parameterisation)

5

Digital input "A−"/"pulse"
See 1

6

Differential input for reset "Z+"

7

Differential input for reset "Z−"

SLIO002

8

Digital input "B−"/"direction"
See 4

Technical data

EPM−S602: rated data

Module identifier

2242

dec

Current consumption/power loss

Current consumption from backplane bus

70 mA

Power loss

0.85 W

Digital inputs

Number of inputs

0

Cable length

shielded

100 m

Load voltage

Nominal value

DC 20.4 ... 28.8 V

Current consumption from load voltage
L+

20 mA (without load)