4 technical data, Technical data, Technical data 4 – Lenze I/O system 1000 System Manual User Manual
Page 238: 4technical data
Technical data
4
l
238
EDSIO1000 EN 7.0
4
Technical data
)
Note!
The technical data of the I/O system modules can be found in the individual
module descriptions which are provided in the "Product description" chapter.
General data
Conformity and approval
Conformity
CE
2006/95/EG
Low−Voltage Directive
Approval
UL
UL 508
File No. E343358
Other
RoHS
−
Products lead−free in accordance with EC Directive
2002/95/EC
Protection of persons and device protection
Degree of protection
IP20
Electrical isolation
To the fieldbus
Electrically isolated
To the process level
Electrically isolated
Insulation resistance
IEC 61131−2
Insulation voltage
against reference earth
of the inputs/outputs
AC / DC 50V, for test voltage AC 500V
Protective measures
Against short circuit
EMC
Noise emission
EN 61000−6−4
Class A (industrial premises)
Noise immunity Zone B
EN 61000−6−2
Industrial premises
EN 61000−4−2
ESD; severity: 3, i.e.
8 kV in the case of air discharge,
4 kV in the case of contact discharge
EN 61000−4−3
RF interference (housing)
80 MHz
1000 MHz, 10 V/m 80 % AM (1 kHz)
EN 61000−4−4
Burst, severity: 3
EN 61000−4−5
Surge, severity 3 *
EN 61000−4−6
RF conducted
150 kHz
80 MHz, 10 V/m 80 % AM (1 kHz)
*
Due to the high−energy single current pulses, a surge requires a suitable external connection with lightning
protection elements like for instance lightning conductors and overvoltage arresters.