Profinet communication – Lenze I/O system 1000 System Manual User Manual
Page 650
PROFINET communication
Parameterising the temperature measurement
Four (two) analog inputs for resistance tests − EPM−S404
l
650
EDSIO1000 EN 7.0
Range
Signal range
Measured value
Measuring range
Range
Signal range
Measured value
(Fct. no.)
3−wire: NI1000
(5B
h
)
+295 °C
+2950
dec
Overflow
−60 ... +250 °C
−600 ... +2500
dec
Nominal range
−105 °C
−1050
dec
Underflow
4−wire: PT100
(60
h
)
+1000 °C
+10000
dec
Overflow
−200 ... +850 °C
−2000 ... +8500
dec
Nominal range
−243 °C
−2430
dec
Underflow
4−wire: PT1000
(61
h
)
+1000 °C
+10000
dec
Overflow
−200 ... +850 °C
−2000 ... +8500
dec
Nominal range
−243 °C
−2430
dec
Underflow
4−wire: NI100
(62
h
)
+295 °C
+2950
dec
Overflow
−60 ... +250 °C
−600 ... +2500
dec
Nominal range
−105 °C
−1050
dec
Underflow
4−wire: NI1000
(63
h
)
+295 °C
+2950
dec
Overflow
−60 ... +250 °C
−600 ... +2500
dec
Nominal range
−105 °C
−1050
dec
Underflow
2−wire: 0 ... 60
W
(70
h
)
−
−
Overflow
0 ... 60
W
0 ... 32767
dec
Nominal range
−
−
Underflow
2−wire: 0 ... 600
W
(71
h
)
−
−
Overflow
0 ... 600
W
0 ... 32767
dec
Nominal range
−
−
Underflow
2−wire: 0 ... 3000
W
(72
h
)
−
−
Overflow
0 ... 3000
W
0 ... 32767
dec
Nominal range
−
−
Underflow
3−wire: 0 ... 60
W
(78
h
)
−
−
Overflow
0 ... 60
W
0 ... 32767
dec
Nominal range
−
−
Underflow
3−wire: 0 ... 600
W
(79
h
)
−
−
Overflow
0 ... 600
W
0 ... 32767
dec
Nominal range
−
−
Underflow
3−wire: 0 ... 3000
W
(7A
h
)
−
−
Overflow
0 ... 3000
W
0 ... 32767
dec
Nominal range
−
−
Underflow
4−wire: 0 ... 60
W
(80
h
)
−
−
Overflow
0 ... 60
W
0 ... 32767
dec
Nominal range
−
−
Underflow
4−wire: 0 ... 600
W
(81
h
)
−
−
Overflow
0 ... 600
W
0 ... 32767
dec
Nominal range
−
−
Underflow
4−wire: 0 ... 3000
W
(82
h
)
−
−
Overflow
0 ... 3000
W
0 ... 32767
Nominal range
−
−
Underflow
2−wire: 0 ... 60
W
(90
h
)
−
−
Overflow
0 ... 60
W
0 ... 6000
dec
Nominal range
−
−
Underflow