9 parameterising the temperature measurement, Parameterising the temperature measurement, Canopen communication – Lenze I/O system 1000 System Manual User Manual
Page 299
CANopen communication
Parameterising the temperature measurement
Four (two) analog inputs for resistance tests − EPM−S404
l
299
EDSIO1000 EN 7.0
8.9
Parameterising the temperature measurement
8.9.1
Four (two) analog inputs for resistance tests − EPM−S404
Parameter data
Index/sub
index
Name
Description/value
Lenze
0x3100/x Diagnostics
A diagnostic alarm occurs if the same event triggers a further
process alarm during a process alarm processing.
Bits 0 ... 5: Reserved
Bit 6: diagnostic alarm (0 = inhibited; 1 = enabled)
Bit 7: Reserved
00
h
0x3101/x Wire−breakage
detection
Bit 0: Channel 1 (0 = inhibited; 1 = enabled)
:
Bit 3: Channel 4
Bits 4 ... 7: Reserved
00
h
0x3102/x Limit value
monitoring
Bit 0: Channel 1 (0 = inhibited; 1 = enabled)
:
Bit 3: Channel 4
Bit 4 ... 7: Reserved
00
h
0x3103/x Reserved
0x3104/x Temperature system
Bit 0, 1: 00
b
= °C; 01
b
= °F; 10
b
= K
Bits 2 ... 7: Reserved
00
h
0x3105/x Interference
frequency
suppression
Bit 0, 1: 01
b
= 60 Hz; 10
b
= 50 Hz
Bits 2 ... 7: Reserved
02
h