CANopen communication

Parameterising the temperature measurement

Four (two) analog inputs for resistance tests − EPM−S404

8

l

299

EDSIO1000 EN 7.0

8.9

Parameterising the temperature measurement

8.9.1

Four (two) analog inputs for resistance tests − EPM−S404

Parameter data

Index/sub
index

Name

Description/value

Lenze

0x3100/x Diagnostics

A diagnostic alarm occurs if the same event triggers a further
process alarm during a process alarm processing.
Bits 0 ... 5: Reserved
Bit 6: diagnostic alarm (0 = inhibited; 1 = enabled)
Bit 7: Reserved

00

h

0x3101/x Wire−breakage

detection

Bit 0: Channel 1 (0 = inhibited; 1 = enabled)
:
Bit 3: Channel 4
Bits 4 ... 7: Reserved

00

h

0x3102/x Limit value

monitoring

Bit 0: Channel 1 (0 = inhibited; 1 = enabled)
:
Bit 3: Channel 4
Bit 4 ... 7: Reserved

00

h

0x3103/x Reserved

0x3104/x Temperature system

Bit 0, 1: 00

b

= °C; 01

b

= °F; 10

b

= K

Bits 2 ... 7: Reserved

00

h

0x3105/x Interference

frequency
suppression

Bit 0, 1: 01

b

= 60 Hz; 10

b

= 50 Hz

Bits 2 ... 7: Reserved

02

h