Product description, Stop, Bus coupler modules canopen − epm−s110 – Lenze I/O system 1000 System Manual User Manual

Page 33: Terminals

background image

Product description

Bus coupler modules

CANopen − EPM−S110

3

l

33

EDSIO1000 EN 7.0

Terminals

Module terminals, spring terminals

2

View

Designation

Explanation

Terminal data

2

6

3

7

4

8

1

5

1

5

4

8

1

Not assigned

10 mm

0.08 ... 1.5 mm²

(AWG 28 ... 16)

2

I/O supply +24 V DC

3

I/O supply 0 V

4

Electronic supply +24 V DC

5

Not assigned

6

I/O supply +24 V DC

7

I/O supply 0 V

SLIO002

8

Electronic supply 0 V

)

Note!

ƒ

Terminals 2 and 6 as well as 3 and 7 are bridged internally. Please note that
the max. permissible bridge current is 5 A.

ƒ

Both the I/O supply and the electronic supply are protected against overload
internally by a fuse. When the fuses have been tripped, the main supply of
the bus coupler (EPM−S700) must be replaced (

726).

System bus (CAN) / CANopen ("CAN"), 9−pole Sub−D plug

5

View

Pin

Assignment

Explanation

1

2

3

4

5

6

7

8

9

1

Not assigned

2

CAN−LOW

Data line

3

CAN−GND

Data ground

4

Not assigned

5

Not assigned

6

Not assigned

7

CAN−HIGH

Data line

8

Not assigned

epm−t023

9

Not assigned

(

Stop!

Housing breakage in the case of a too high tightening torque of the securing
screws
If the connector securing screws are tightened too firmly, the housing may
break.
Possible consequences:

ƒ

The plug connection is no longer secured against tension.

ƒ

Enclosure IP20 of the module which is warranted can no longer be
guaranteed.

Protective measures:

ƒ

Tighten securing screws without using force (max. 40 Nm).