beautypg.com

Appendix – Lenze I/O system 1000 System Manual User Manual

Page 734

background image

Appendix

Serial process interfacing
Principle of backplane bus communication

15

l

734

EDSIO1000 EN 7.0

Write fragment

Higher−level system

EPM−S640/EPM−S650

Description

Byte

Function

Byte

Function

0

Control byte

Bits 3...0:
0

h

... 7

h

= fragment number

8

h

= idle state, no data available.

B

h

= carry out a reset on the EPM−S6x0.

Bits 7...4:
Reserved for reception.

1 ... n−1

User data

User data; n = number of the bytes
assigned in the address range (IO size)

®
¬

0

Acknowledgement
/ status

Bits 3...0:
Reserved for reception.
Bits 7...4:
0

h

... 7

h

= acknowledgement fragment

number
8

h

: acknowledgement, idle state

9

h

: fragmented transmission started.

C

h

: status, reset was carried out on

EPM−S6x0.
D

h

: status, the length specified is invalid.

E

h

: status, EPM−S6x0 communication

error, partner is not responding.

Write last fragment

Higher−level system

EPM−S640/EPM−S650

Description

Byte

Function

Byte

Function

0

Control byte

Bits 3...0:
8

h

= idle state, no data available.

A

h

= transmission of last fragment.

B

h

= carry out a reset on the EPM−S6x0.

Bits 7...4:
Reserved for reception.

1 ... n−1

User data

User data; n = number of the bytes
assigned in the address range (IO size)

®
¬

0

Acknowledgement
/ status

Bits 3...0:
Reserved for reception.
Bits 7...4:
8

h

: acknowledgement, idle state

A

h

: acknowledgement, last fragment

received.
C

h

: status, reset was carried out on

EPM−S6x0.
D

h

: status, the length specified is invalid.

E

h

: status, EPM−S6x0 communication

error, partner is not responding.