beautypg.com

3 repair, 1 replacing the electronic module/main supply, Replacing the electronic module/main supply – Lenze I/O system 1000 System Manual User Manual

Page 726: Maintenance

background image

Maintenance

Repair
Replacing the electronic module/main supply

14

l

726

EDSIO1000 EN 7.0

14.3

Repair

14.3.1

Replacing the electronic module/main supply

)

Note!

If an I/O compound module is defective, just replace its electronic module.
Leave the base module and the wiring unchanged.
The input fuse of the power supply module is located in the electronic module.
If this fuse has tripped, the electronic module needs to be replaced. The same
applies to the main supply which is integrated in bus coupler modules.

SLIO022

Fig. 14−1

Replacing the electronic module

How to proceed:

1. Press the locking button underneath the electronic module (or, in the case of bus

coupler modules, the main supply, respectively) and remove the electronic module
from the base module at the same time.

2. Slide a new electronic module of the same type on the base module until it locks

into place.