5 pdo mapping, Pdo mapping, Canopen communication – Lenze I/O system 1000 System Manual User Manual

Page 258: Transmitting process data pdo mapping

background image

CANopen communication

Transmitting process data
PDO mapping

8

l

258

EDSIO1000 EN 7.0

8.3.5

PDO mapping

The PDO mapping differs depending on the motion control to be configured:

Drive−based automation

(decentralised, with intelligent controllers)

Controller−based automation

(with a central control)

l

Direct data exchange between the IO system and
the controller without a master control.
Configuration with L−force Engineer

l

Direct data exchange between the IO system and
the control (IPC). Configuration via L−force PLC
Designer

l

Static PDO mapping (default setting)

l

Free mapping by means of a bus configurator (e.g.
PLC Designer)

l

Up to 10 RPDOs and TPDOs can be used

l

Up to 16 RPDOs and TPDOs can be used

The following representation describes the static PDO mapping (Drive−based automation)
by means of an example station structure:

Structure

Module

CANopen

2 x DI 8 x DI 4 × DI 2 × DI 8 × DI 8 × DI 8 × DI 8 × DI 2 × DI 8 × DI 2 x AI

4 x AI 8xDO

2 x

DO

No.

M0

M1

M2

M3

M4

M5

M6

M7

M8

M9

M10

M11

M12

M13

M14

n x DI

I/O compound module with n digital inputs

n x DO

I/O compound module with n digital outputs

n x AI

I/O compound module with n analog inputs

n x AO

I/O compound module with n analog outputs

Process image

Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

PDO1

Permanent for the first DI or
DO

RPDO1

M13

M14

TPDO1

M1

M2

M3M4

M5

M6

M7

M8

M9

PDO2

Permanent for the first AI or
AO

RPDO2

TPDO2

M11

M11

M11

M11

M12

M12

M12

M12

PDO3

DI/DO, DI/DO time stamp,
DO PWM, AI/AO, counter, SSI,
RS232, RS485

RPDO3

TPDO3

M12

M12

M12

M12

PDO4

DI/DO, DI/DO time stamp,
DO PWM, AI/AO, counter, SSI,
RS232, RS485

RPDO4

TPDO4

M10

...

...

...

PDO10

DI/DO, DI/DO time stamp,
DO PWM, AI/AO, counter, SSI,
RS232, RS485

RPDO10

TPDO10