DeviceNet communication

Setting the parameters of analog I/O
2 analog inputs −10 ... +10 V (16 bits) − EPM−S406

11

l

568

EDSIO1000 EN 7.0

Measuring range

Voltage (U)

Decimal (D)

Hex

Range

Conversion

(Fct. no.)

[V]

−10 ... +10 V

(12

h

)

11.76

32511

7EFF

Overflow

U = D * 10 / 27648
D = 27648 * U / 10

10

27648

6C00

Nominal range

5

13824

3600

0

0

0000

−5

−13824

CA00

−10

−27648

9400

−11.76

−32512

8100

Underflow

−10 ... +10 V

(22

h

)

12.5

20480

5000

Overflow

U = D * 10 / 16384
D = 16384 * U / 10

10

16384

4000

Nominal range

5

8192

2000

0

0

0000

−5

−8192

E000

−10

−16384

C000

−12.5

−20480

B000

Underflow

0 ... 10 V

(10

h

)

11.76

32511

7EFF

Overflow

U = D * 10 / 27648
D = 27648 * U / 10

10

27648

6C00

Nominal range

5

13824

3600

0

0

0000

−1.76

−4864

ED00

Underflow

0 ... 10 V

(20

h

)

12.5

20480

5000

Overflow

U = D * 10 / 16384
D = 16384 * U / 10

10

16384

4000

Nominal range

5

8192

2000

0

0

0000

−2

−3277

F333

Underflow