Page 284: Parameterising digital i/os, Canopen communication, Digital inputs are parameterised via index i6002h, Digital outputs are parameterised via index i6202, The subindex depends on the slot

background image

CANopen communication

General function of the parameter setting
Parameterising digital I/Os

8

l

284

EDSIO1000 EN 7.0

8.7

General function of the parameter setting

8.7.1

Parameterising digital I/Os

The parameter data of the digital I/O define if the control signals are to be transmitted with
original or inverted polarity.

For parameter data, 1 byte is available which is assigned via SDO.

ƒ

Digital inputs are parameterised via index I6002h.

ƒ

Digital outputs are parameterised via index I6202

h

.

The subindex depends on the slot.

Index

I6002

h

h

I6202

Subindex

1

Subindex

2

Subindex

64

Module 1

Module 2

Module 64

00

00

00

h

h

h

Byte 0

Byte 0

Byte 0

Bit

Bit

Bit

0

0

0

1

1

1

2

2

2

3

3

3

4

4

4

5

5

5

6

6

6

7

7

7

...

SLIO012

Fig. 8−12

Display of the digital I/O parameter data

Byte

Assignment

Lenze setting

0

Polarity of the transmitted
signals

Bit0

0

Signal is transmitted in original
form

00

h

1

Signal is transmitted in inverse
form

Bit 1...7

Reserve

)

Note!

Store changed parameters in the EEPROM via index I1010

h

. The settings are

maintained after the supply voltage is switched off.