Product description – Lenze I/O system 1000 System Manual User Manual
Page 228
Product description
I/O compound modules − communication
RS485 interface − EPM−S650
l
228
EDSIO1000 EN 7.0
Parameterisable idle level:
For a connection with minimum reflections and the open circuit detection in RS422/485
operation, the cables can be pre−assigned via parameters with a defined idle level.
The receiver is connected as follows:
Parameter
Description
Receiver connection
None
No pre−assignment of the receive
path. This setting is only advisable
for special drivers that are provided
with a bus capability.
Signal R(A) 5 V (open circuit detection)
Signal R(B) 0 V
If this pre−assignment is set, open
circuit detection is possible in full
duplex operation (RS422).
Signal R(A) 0 V
Signal R(B) 5 V
This pre−assignment corresponds to
the idle state (no transmitter active)
in half duplex operation under
RS485. Open circuit detection is not
possible.
Technical data
EPM−S650: Rated data
Module identifier
2625
dec
Current consumption/power loss
Current consumption from backplane bus
100 mA
Current consumption from load voltage L+
10 mA (without load)
Power loss
1 W
Status, alarm, diagnostics
Status display
Yes
Alarms
Yes, parameterisable
Process alarm
No
Diagnostic alarm
Yes, parameterisable
Diagnostic function
Yes, parameterisable
Diagnostic information can be read out
Possible
Module status
Green LED
Module error display
Red LED
Channel error display
Red LED
Communication
Interface
RS422 and RS485
Electrical isolation
To the backplane bus
PtP communication
Yes
20 mA / TTY
No
Transmission speed
150 bps ... 115.2 kbps
Cable length, max.
1200 m