Product description

I/O compound modules − communication
RS485 interface − EPM−S650

3

l

228

EDSIO1000 EN 7.0

Parameterisable idle level:

For a connection with minimum reflections and the open circuit detection in RS422/485
operation, the cables can be pre−assigned via parameters with a defined idle level.

The receiver is connected as follows:

Parameter

Description

Receiver connection

None

No pre−assignment of the receive
path. This setting is only advisable
for special drivers that are provided
with a bus capability.

Signal R(A) 5 V (open circuit detection)
Signal R(B) 0 V

If this pre−assignment is set, open
circuit detection is possible in full
duplex operation (RS422).

Signal R(A) 0 V
Signal R(B) 5 V

This pre−assignment corresponds to
the idle state (no transmitter active)
in half duplex operation under
RS485. Open circuit detection is not
possible.

Technical data

EPM−S650: Rated data

Module identifier

2625

dec

Current consumption/power loss

Current consumption from backplane bus

100 mA

Current consumption from load voltage L+

10 mA (without load)

Power loss

1 W

Status, alarm, diagnostics

Status display

Yes

Alarms

Yes, parameterisable

Process alarm

No

Diagnostic alarm

Yes, parameterisable

Diagnostic function

Yes, parameterisable

Diagnostic information can be read out

Possible

Module status

Green LED

Module error display

Red LED

Channel error display

Red LED

Communication

Interface

RS422 and RS485

Electrical isolation

To the backplane bus

PtP communication

Yes

20 mA / TTY

No

Transmission speed

150 bps ... 115.2 kbps

Cable length, max.

1200 m