beautypg.com

9 time stamp parameterising, Ethercat kommunikation – Lenze I/O system 1000 System Manual User Manual

Page 521

background image

EtherCAT Kommunikation

Time stamp parameterising

2 digital inputs with time stamp function − EPM−S207

10

l

521

EDSIO1000 EN 7.0

10.9

Time stamp parameterising

10.9.1

2 digital inputs with time stamp function − EPM−S207

Parameter data

Subindex

Name

Description/value

Lenze

01

Length − process
image input data

Length of input data (backplane bus communication); the values
are specified by the system. Other values are not permissible.

14

h

or 3C

h

(fix)

02

Length − process
image output data

Length of output data (backplane bus communication); the
values are specified by the system. Other values are not
permissible.

00

h

(fix)

03

Input delay DI 0

00

h

= 1

ms

02

h

= 3

ms

04

h

= 10

ms

07

h

= 86

ms

09

h

= 342

ms

0C

h

= 273

ms

Other values are not permissible.

02

h

04

Input delay DI 1

02

h

05

Edge 0−1 an DI x

Time stamp entry on rising edge
Bit 0: DI 0 (0: inhibit, 1 = enable)
Bit 1: DI 1 (0: inhibit, 1 = enable)
Bits 7 ... 2: Reserved

00

h

06

Edge 1−0 at DI x

Time stamp entry on falling edge
Bit 0: DI 0 (0: inhibit, 1 = enable)
Bit 1: DI 1 (0: inhibit, 1 = enable)
Bits 7 ... 2: Reserved

00

h

10.9.2

2 digital outputs with time stamp function − EPM−S310

Parameter data

Subindex

Name

Description/value

Lenze

01

Length − process
image input data

Length of input data (backplane bus communication); the values
are specified by the system. Other values are not permissible.

14

h

or 3C

h

(fix)

02

Length − process
image output data

Length of output data (backplane bus communication); the
values are specified by the system. Other values are not
permissible.

00

h

(fix)