9 time stamp parameterising, Ethercat kommunikation – Lenze I/O system 1000 System Manual User Manual
Page 521
![background image](/manuals/565636/521/background.png)
EtherCAT Kommunikation
Time stamp parameterising
2 digital inputs with time stamp function − EPM−S207
l
521
EDSIO1000 EN 7.0
10.9
Time stamp parameterising
10.9.1
2 digital inputs with time stamp function − EPM−S207
Parameter data
Subindex
Name
Description/value
Lenze
01
Length − process
image input data
Length of input data (backplane bus communication); the values
are specified by the system. Other values are not permissible.
14
h
or 3C
h
(fix)
02
Length − process
image output data
Length of output data (backplane bus communication); the
values are specified by the system. Other values are not
permissible.
00
h
(fix)
03
Input delay DI 0
00
h
= 1
ms
02
h
= 3
ms
04
h
= 10
ms
07
h
= 86
ms
09
h
= 342
ms
0C
h
= 273
ms
Other values are not permissible.
02
h
04
Input delay DI 1
02
h
05
Edge 0−1 an DI x
Time stamp entry on rising edge
Bit 0: DI 0 (0: inhibit, 1 = enable)
Bit 1: DI 1 (0: inhibit, 1 = enable)
Bits 7 ... 2: Reserved
00
h
06
Edge 1−0 at DI x
Time stamp entry on falling edge
Bit 0: DI 0 (0: inhibit, 1 = enable)
Bit 1: DI 1 (0: inhibit, 1 = enable)
Bits 7 ... 2: Reserved
00
h
10.9.2
2 digital outputs with time stamp function − EPM−S310
Parameter data
Subindex
Name
Description/value
Lenze
01
Length − process
image input data
Length of input data (backplane bus communication); the values
are specified by the system. Other values are not permissible.
14
h
or 3C
h
(fix)
02
Length − process
image output data
Length of output data (backplane bus communication); the
values are specified by the system. Other values are not
permissible.
00
h
(fix)