beautypg.com

Profinet communication – Lenze I/O system 1000 System Manual User Manual

Page 669

background image

PROFINET communication

Parameterising the counter

Two counters 32 bits, 24 V DC − EPM−S601

12

l

669

EDSIO1000 EN 7.0

Read data: 12 bytes

Input area in the process image

Addr.

Access

Assignment

+0

Double word

Counter 1: count value

+4

Double word

Counter 2: count value

+8

Word

Counter 1: status word (see following table)

+10

Word

Counter 2: status word (see following table)

Count value: Current counter content

EPM−S601 status word

Bit

Designation

Function

0

Reserved

1

STS_CTRL_COMP

Is set if the comparison bit is enabled

2

STS_SW−GATE

Software gate status (set if SW gate active)

3

Reserved

4

Reserved

5

STS_GATE

Status of internal gate (set if internal gate active)

6

STS_COMP

Status of comparison bit

7

STS_C_DN

Status set for counter direction backwards

8

STS_C_UP

Status set for counter direction forwards

9

STS_CMP*

Comparator status is set if the comparison condition is met.
If the comparison is deactivated (counter mode byte 1 = 000

b

), the bit has

no function.

10

STS_END*

Status set if final value was reached

11

STS_OFLW*

Status set in the case of overflow

12

STS_UFLW*

Status set in the case of underflow

13

STS_ZP*

Status set in the case of zero crossing

14

Reserved

15

Reserved

*

The bits are set until reset with RES_SET (bit 6 control word)

Write data: 12 bytes

Output area in the process image

Addr.

Access

Assignment

+0

Double word

Counter 1: Comparison value

+4

Double word

Counter 2: Comparison value

+8

Word

Counter 1: Control word (see following table)

+10

Word

Counter 2: Control word (see following table)

Comparison value: With the comparison value you can specify a value which, by
comparison with the current counter content, can impact the counter output or trigger a
process alarm. The response of the comparison bit STS_COMP in the counter status or the
process alarm is to be specified via data set 80

h

for counter 0 and 82

h

for counter 1.