EtherCAT Kommunikation

Parameterising the temperature measurement

Four (two) analog inputs for resistance tests − EPM−S404

10

l

503

EDSIO1000 EN 7.0

Range

Signal range

Measured value

Measuring range

Range

Signal range

Measured value

(Fct. no.)

3−wire: 0 ... 60

W

(98

h

)

Overflow

0 ... 60

W

0 ... 6000

dec

Nominal range

Underflow

3−wire: 0 ... 600

W

(99

h

)

Overflow

0 ... 600

W

0 ... 6000

dec

Nominal range

Underflow

3−wire: 0 ... 3000

W

(9A

h

)

Overflow

0 ... 3000

W

0 ... 30000

dec

Nominal range

Underflow

4−wire: 0 ... 60

W

(A0

h

)

Overflow

0 ... 60

W

0 ... 6000

dec

Nominal range

Underflow

4−wire: 0 ... 600

W

(A1

h

)

Overflow

0 ... 600

W

0 ... 6000

dec

Nominal range

Underflow

4−wire: 0 ... 3000

W

(A2

h

)

Overflow

0 ... 3000

W

0 ... 30000

dec

Nominal range

Underflow

2−wire: 0 ... 60

W

(D0

h

)

70.55

W

32511

dec

Overflow

0 ... 60

W

0 ... 27648

dec

Nominal range

Underflow

2−wire: 0 ... 600

W

(D1

h

)

705.5

W

32511

dec

Overflow

0 ... 600

W

0 ... 27648

dec

Nominal range

Underflow

2−wire: 0 ... 3000

W

(D2

h

)

3528

W

32511

dec

Overflow

0 ... 3000

W

0 ... 27648

dec

Nominal range

Underflow

3−wire: 0 ... 60

W

(D8

h

)

70.55

W

32511

dec

Overflow

0 ... 60

W

0 ... 27648

dec

Nominal range

Underflow

3−wire: 0 ... 600

W

(D9

h

)

705.5

W

32511

dec

Overflow

0 ... 600

W

0 ... 27648

dec

Nominal range

Underflow

3−wire: 0 ... 3000

W

(DA

h

)

3528

W

32511

dec

Overflow

0 ... 3000

W

0 ... 27648

dec

Nominal range

Underflow

4−wire: 0 ... 60

W

(E0

h

)

70.55

W

32511

dec

Overflow

0 ... 60

W

0 ... 27648

dec

Nominal range

Underflow

4−wire: 0 ... 600

W

(E1

h

)

705.5

W

32511

dec

Overflow

0 ... 600

W

0 ... 27648

dec

Nominal range

Underflow

4−wire: 0 ... 3000

W

(E2

h

)

3528

W

32511

dec

Overflow

0 ... 3000

W

0 ... 27648

dec

Nominal range

Underflow