Product description, Bus coupler modules ethercat − epm−s130, Terminals – Lenze I/O system 1000 System Manual User Manual
Page 47: Technical data
Product description
Bus coupler modules
EtherCAT − EPM−S130
l
47
EDSIO1000 EN 7.0
Terminals
Module terminals, spring terminals
2
View
Designation
Explanation
Terminal data
2
6
3
7
4
8
1
5
1
5
4
8
1
Not assigned
10 mm
0.08 ... 1.5 mm²
(AWG 28 ... 16)
2
I/O supply +24 V DC
3
I/O supply 0 V
4
Electronic supply +24 V DC
5
Not assigned
6
I/O supply +24 V DC
7
I/O supply 0 V
SLIO002
8
Electronic supply 0 V
)
Note!
ƒ
Terminals 2 and 6 as well as 3 and 7 are bridged internally. Please note that
the max. permissible bridge current is 5 A.
ƒ
Both the I/O supply and the electronic supply are protected against overload
internally by a fuse. When the fuses have been tripped, the main supply of
the bus coupler (EPM−S700) must be replaced (
¶ 726).
EtherCAT, RJ45 socket
4, 5
View
Pin
Assignment
Explanation
8
1
1
Transmit +
Transmitted data plus
2
Transmit −
Transmitted data minus
3
Receive +
Received data plus
4
−
Not assigned
5
−
Not assigned
6
Receive −
Received data minus
7
−
Not assigned
8
−
Not assigned
SLIO065
9
−
Not assigned
Technical data
EPM−S130: rated data
Electrical data
Supply voltage
Nominal value
DC 24 V
Permissible range
DC 20.4 ... 28.8 V
Current consumption
Nominal value
0.95 A
In idle state
0.095 A
Starting current
2.8 A
I
2
t
0.25 A
2
s
Current output, max.
At the backplane bus
3 A
Load supply
7 A (if no UL conformity is required: max. 10 A)
Polarity reversal protection
No
Power loss
3 W