beautypg.com

Product description, Bus coupler modules ethercat − epm−s130, Terminals – Lenze I/O system 1000 System Manual User Manual

Page 47: Technical data

background image

Product description

Bus coupler modules

EtherCAT − EPM−S130

3

l

47

EDSIO1000 EN 7.0

Terminals

Module terminals, spring terminals

2

View

Designation

Explanation

Terminal data

2

6

3

7

4

8

1

5

1

5

4

8

1

Not assigned

10 mm

0.08 ... 1.5 mm²

(AWG 28 ... 16)

2

I/O supply +24 V DC

3

I/O supply 0 V

4

Electronic supply +24 V DC

5

Not assigned

6

I/O supply +24 V DC

7

I/O supply 0 V

SLIO002

8

Electronic supply 0 V

)

Note!

ƒ

Terminals 2 and 6 as well as 3 and 7 are bridged internally. Please note that
the max. permissible bridge current is 5 A.

ƒ

Both the I/O supply and the electronic supply are protected against overload
internally by a fuse. When the fuses have been tripped, the main supply of
the bus coupler (EPM−S700) must be replaced (

726).

EtherCAT, RJ45 socket

4, 5

View

Pin

Assignment

Explanation

8

1

1

Transmit +

Transmitted data plus

2

Transmit −

Transmitted data minus

3

Receive +

Received data plus

4

Not assigned

5

Not assigned

6

Receive −

Received data minus

7

Not assigned

8

Not assigned

SLIO065

9

Not assigned

Technical data

EPM−S130: rated data

Electrical data

Supply voltage

Nominal value

DC 24 V

Permissible range

DC 20.4 ... 28.8 V

Current consumption

Nominal value

0.95 A

In idle state

0.095 A

Starting current

2.8 A

I

2

t

0.25 A

2

s

Current output, max.

At the backplane bus

3 A

Load supply

7 A (if no UL conformity is required: max. 10 A)

Polarity reversal protection

No

Power loss

3 W