Canopen communication, Index table – Lenze I/O system 1000 System Manual User Manual
Page 372

CANopen communication
Index table
l
372
EDSIO1000 EN 7.0
Important
Possible settings
Name
Index
Selection
Lenze
I1803
h
¿
^ 256
1 COB−ID used
by TxPDO 4
1152
+ NID
385
{1}
2047 Definition of specific identifiers
for process data object 4 (NID=
Node ID / node address)
2 Transmission
type
255
0
{1}
255 Defining the transmission mode
0
Function deactivated
The output data are accepted on
sync telegram transmission.
1 ...
240
Process data transfer after sync no. 1
...
Process data transfer after sync no.
240
The output data are accepted
after transmission of the set
number (1 ... 240) of sync
telegrams.
254
Time−controlled process data transfer
Only if a cycle time is set in
I180x
h
, subindex 5
255
Event−controlled process data transfer
255
Event−controlled process data transfer
with cyclic overlay
Only if a cycle time is set in
I180x
h
, subindex 5
3 Inhibit time
0
0
{1 ms}
65535 Blocking time
5 Event time
0
0
{1 ms}
65535 Cycle time
I1804
h
¿
^ 256
1 COB−ID used
by TxPDO 5
1664
+ NID
385
{1}
2047 Definition of specific identifiers
for process data object 5 (NID=
Node ID / node address)
2 Transmission
type
255
0
{1}
255 Defining the transmission mode
0
Function deactivated
The output data are accepted on
sync telegram transmission.
1 ...
240
Process data transfer after sync no. 1
...
Process data transfer after sync no.
240
The output data are accepted
after transmission of the set
number (1 ... 240) of sync
telegrams.
254
Time−controlled process data transfer
Only if a cycle time is set in
I180x
h
, subindex 5
255
Event−controlled process data transfer
255
Event−controlled process data transfer
with cyclic overlay
Only if a cycle time is set in
I180x
h
, subindex 5
3 Inhibit time
0
0
{1 ms}
65535 Blocking time
5 Event time
0
0
{1 ms}
65535 Cycle time