Product description
I/O compound modules − digital I/O
2 digital outputs with time stamp function − EPM−S310
l
103
EDSIO1000 EN 7.0
Technical data
EPM−S310: rated data
Module identifier
3905
dec
Current consumption/power loss
Current consumption from backplane bus
85 mA
Power loss
0.95 W
Digital outputs
Number of outputs
2
Cable length
shielded
1000 m
unshielded
600 m
Load voltage
Nominal value
DC 24 (DC 20.4 ... 28.8 V)
Current consumption from load voltage
L+
15 mA (without load)
Total current
for each group, horizontal structure,
40°C
1 A
for each group, horizontal structure,
60°C
1 A
for each group, vertical structure
1 A
Output current
for "1" signal, nominal value
0.5 A
Output delay
from "0" to "1"
Max. 100 ns
from "1" to "0"
Max. 100 ns
Lamp load
10 W
Parallel switching of outputs
for redundant control
Not possible
for power increase
Not possible
Control of a digital input
Possible
Switching frequencies
for ohmic loads
Max. 40 Hz
for inductive loads
Max. 40 Hz
for lamp loads
Max. 40 Hz
Limitation (internal) of the inductive
breaking voltage
L+ (−52 V)
Short circuit protection of the output
Electronically; only highside
Operating threshold of the protection
system
2.5 A
Output data size