EtherCAT Kommunikation

Parameterising the temperature measurement
Four (two) analog inputs for resistance tests − EPM−S404

10

l

498

EDSIO1000 EN 7.0

10.6

Parameterising the temperature measurement

10.6.1

Four (two) analog inputs for resistance tests − EPM−S404

Parameter data

Subindex

Name

Description/value

Lenze

01

Diagnostics

A diagnostic alarm occurs if the same event triggers a further
process alarm during a process alarm processing.
Bits 0 ... 5: Reserved
Bit 6: diagnostic alarm (0 = inhibited; 1 = enabled)
Bit 7: Reserved

00

h

02

Wire−breakage
detection

Bit 0: Channel 1 (0 = inhibited; 1 = enabled)
:
Bit 3: Channel 4
Bits 4 ... 7: Reserved

00

h

03

Limit value
monitoring

Bit 0: Channel 1
(0 = inhibited; 1 = enabled)
:
Bit 3: Channel 4
Bits 4 ... 7: Reserved

00

h

04

Reserved

05

Temperature system

Bit 0, 1: 00

b

= °C; 01

b

= °F; 10

b

= K

Bits 2 ... 7: Reserved

00

h

06

Interference
frequency
suppression

Bit 0, 1: 01

b

= 60 Hz; 10

b

= 50 Hz

Bits 2 ... 7: Reserved

02

h