PROFIBUS communication

Parameterising technology modules

RS485 interface − EPM−S650

9

l

479

EDSIO1000 EN 7.0

Diagnostic data

Since this module does not support alarms, the diagnostic data provides information
about this module.

In the event of an error the corresponding channel LED of the module is lit and the error is
entered in the diagnostic data.

Diagnostic data − data set 01h

Name

Byte

Function

Default

ERR_A

1

ERR_A−diagnostics
Bit 0: Set in the case of module fault
Bit 1: Set in the case of internal error
Bit 2: Set in the case of external error (cable break)
Bit 3: Reserved
Bit 4: Set in the case of a missing external supply voltage
Bit 5, 6: Reserved
Bit 7: Set in the case of parameterisation error

00

h

MODTYP

1

Module information
Byte 0:
Bit 3 ... 0: Module class (0111b: Gateway module)
Bit 4: channel information available
Bits 7 ... 4: 0 reserved

17

h

ERR_C

1

ERR_A−diagnostics
Bit 7 ... 0: Reserved

00

h

ERR_D

1

ERR_D diagnostics
Bit 3 ... 0: Reserved
Bit 4: Set in the case of internal communication error
Bit 7 ... 5: Reserved

00

h

CHTYP

1

Channel type
Bit 7 ... 0: Reserved

00

h

NUMBIT

1

Number of diagnostic bits of the module per channel (here
08

h

)

08

h

NUMCH

1

Number of channels in module
Bit 7 ... 0: Reserved

00

h

CHERR

1

Bit 0: set in the event of an error of channel group 1
Bits 7 ... 1 0 (fixed)

00

h

CH0ERR

8

Channel−specific error: channel x:
Bits 3 ... 0: 0 (fixed)
Bit 4 : set in the case of open circuit (only possible for RS422)
Bits 7 ... 5: 0 (fixed)

00

h

CH1ERR ... CH7ERR

8

Bit 7 ... 0: Reserved

00

h

DIAG_US

4

Value of

ms ticker when diagnostics occur

Bytes 0 ...3

00

h