Profinet communication, Measuring range – Lenze I/O system 1000 System Manual User Manual
Page 649
![background image](/manuals/565636/649/background.png)
PROFINET communication
Parameterising the temperature measurement
Four (two) analog inputs for resistance tests − EPM−S404
l
649
EDSIO1000 EN 7.0
Lenze
Description/value
Name
Data set
Lenze
Description/value
Name
Byte
No.
Channel 2
129
0
Function channel 2
See channel 1
50
h
1
Conversion time
channel 2
See channel 1
00
h
2, 3
Upper limit value
channel 2
See channel 1
7FFF
h
4, 5
Lower limit value
channel 2 (HIGH byte)
8000
h
Channel 3 (for two−wire conductor connections only)
130
0
Function channel 3
See channel 1
50
h
1
Conversion time
channel 3
See channel 1
00
h
2, 3
Upper limit value
channel 3
See channel 1
7FFF
h
4, 5
Lower limit value
channel 3
8000
h
Channel 4 (for two−wire conductor connections only)
131
0
Function channel 4
See channel 1
50
h
1
Conversion time
channel 4
See channel 1
00
h
2, 3
Upper limit value
channel 4
See channel 1
7FFF
h
4, 5
Lower limit value
channel 4
8000
h
Measuring range
Measuring range
Measured value
Signal range
Range
(Fct. no.)
2−wire: PT100
(50
h
)
+1000 °C
+10000
dec
Overflow
−200 ... +850 °C
−2000 ... +8500
dec
Nominal range
−243 °C
−2430
dec
Underflow
2−wire: PT1000
(51
h
)
+1000 °C
+10000
dec
Overflow
−200 ... +850 °C
−2000 ... +8500
dec
Nominal range
−243 °C
−2430
dec
Underflow
2−wire: NI100
(52
h
)
+295 °C
+2950
dec
Overflow
−60 ... +250 °C
−600 ... +2500
dec
Nominal range
−105 °C
−1050
dec
Underflow
2−wire: NI1000
(53
h
)
+295 °C
+2950
dec
Overflow
−60 ... +250 °C
−600 ... +2500
dec
Nominal range
−105 °C
−1050
dec
Underflow
3−wire: PT100
(58
h
)
+1000 °C
+10000
dec
Overflow
−200 ... +850 °C
−2000 ... +8500
dec
Nominal range
−243 °C
−2430
dec
Underflow
3−wire: PT1000
(59
h
)
+1000 °C
+10000
dec
Overflow
−200 ... +850 °C
−2000 ... +8500
dec
Nominal range
−243 °C
−2430
dec
Underflow
3−wire: NI100
(5A
h
)
+295 °C
+2950
dec
Overflow
−60 ... +250 °C
−600 ... +2500
dec
Nominal range
−105 °C
−1050
dec
Underflow