EtherCAT Kommunikation
General function of the parameter setting
l
485
EDSIO1000 EN 7.0
10.4
General function of the parameter setting
Parameterise I/O compound modules using SDO transfer.
Addressing takes place via index 0x3100 + EtherCAT slot no. Subindexes give you access to
the corresponding parameters. The relevant module description contains the subindex
assignment.
Index
Subindex
Name
Type
Attr.
Meaning
0x3100
...
0x313F
0x00
Parameter
Unsigned8
ro
Number of input data
subindexes for the
corresponding EtherCAT slot
no.
0x01
0x02
...
Param1
Param2
ro/rw
ro/rw
Parameter data (see module
description)
If the module is parameterisable, the following applies:
Index 0x3100: access to EtherCAT slot no. 1
Index 0x3101: access to EtherCAT slot no. 2
...
Index 0x313F: access to EtherCAT slot no. 64
The following example shows access to the parameters of the module in slot 4 via index
0x3103.
Phy. slot
1
2
3
4
Module
DI
DI
DO
AI
Index
0x3100*
03101*
0x3102*
0x3103
EtherCAT slot no.
1
−
2
3
*
This entry is not executed because the module is not parameterisable.