Canopen communication, Default mapping – Lenze I/O system 1000 System Manual User Manual

Page 267

background image

CANopen communication

Transmitting process data

PDO mapping for counters and encoder evaluation

8

l

267

EDSIO1000 EN 7.0

Default mapping

PDOx-Rx

PDOx-Rx

PDOx-Tx

PDOx-Tx

EPM

-S1

10

EPM

-S6xx

1

5

9

13

2

6

10

14

3

7

11

15

4

8

12

16

402

h

508

h

382

h

482

h

Node-ID = 2

SLIO047

Fig. 8−8

Mapping contents

Word

EPM−S600

EPM−S601

EPM−S602

EPM−S603

EPM−S604

1

Comparison value

Comparison value

C1

Comparison value

Control word C1

2

Control word C2

3

Set value

Comparison value

C2

Set value

4

5

Control word

Control word C1

Control word

6

Control word C2

7

8

9

Count value

Count value C1

Count value

Count value C1

Encoder value

10

11

Latch value

Count value C2

Status word

Count value C2

Ticker value

12

Ticker value

13

Status word

Status word C1

Status word C1

14

Ticker value

Status word C2

Status word C2

15

16

Comparison value: Here you can select a value which, by comparison with the current
counter content, can impact the counter output or trigger a process alarm. The response
of the output or the process alarm can be parameterised.

Set value:With an edge change 0−1 of COUNTERVAL_SET in the control word, the set value
is accepted in the counter.

Count value: Current counter content

Latch value: If there is a positive edge at the latch input, the count value is stored here.

Ticker value: After mains connection a timer (

ms ticker) is started, which after 65535 ms

starts with 0 again. With every change of the count value the time value of the timer is
stored as 16−bit

ms value together with the count value in the input area.