CANopen communication
Transmitting process data
PDO mapping for counters and encoder evaluation
l
267
EDSIO1000 EN 7.0
Default mapping
PDOx-Rx
PDOx-Rx
PDOx-Tx
PDOx-Tx
EPM
-S1
10
EPM
-S6xx
1
5
9
13
2
6
10
14
3
7
11
15
4
8
12
16
402
h
508
h
382
h
482
h
Node-ID = 2
SLIO047
Fig. 8−8
Mapping contents
Word
EPM−S600
EPM−S601
EPM−S602
EPM−S603
EPM−S604
1
Comparison value
Comparison value
C1
Comparison value
Control word C1
−
2
Control word C2
3
Set value
Comparison value
C2
Set value
−
4
5
Control word
Control word C1
Control word
6
−
Control word C2
−
7
−
8
9
Count value
Count value C1
Count value
Count value C1
Encoder value
10
11
Latch value
Count value C2
Status word
Count value C2
Ticker value
12
Ticker value
13
Status word
Status word C1
−
Status word C1
−
14
Ticker value
Status word C2
Status word C2
15
−
−
−
16
Comparison value: Here you can select a value which, by comparison with the current
counter content, can impact the counter output or trigger a process alarm. The response
of the output or the process alarm can be parameterised.
Set value:With an edge change 0−1 of COUNTERVAL_SET in the control word, the set value
is accepted in the counter.
Count value: Current counter content
Latch value: If there is a positive edge at the latch input, the count value is stored here.
Ticker value: After mains connection a timer (
ms ticker) is started, which after 65535 ms
starts with 0 again. With every change of the count value the time value of the timer is
stored as 16−bit
ms value together with the count value in the input area.