PROFINET communication

Parameterising the temperature measurement

Two analog inputs for thermocouple measurement − EPM−S405

12

l

655

EDSIO1000 EN 7.0

12.7.2

Two analog inputs for thermocouple measurement − EPM−S405

During the execution time you can access the parameter data via the following data sets:

Data set

Name

Description/value

Lenze

No.

Byte

0

0

Diagnostics

A diagnostic alarm occurs if the same event triggers a
further process alarm during a process alarm processing.
Bits 0 ... 5: Reserved
Bit 6: diagnostic alarm (0 = inhibited; 1 = enabled)
Bit 7: Reserved

00

h

1

Wire−breakage
detection

Bit 0: Channel 1 (0 = inhibited; 1 = enabled)
Bit 1: Channel 2
Bits 2 ... 7: Reserved

00

h

2

Limit value
monitoring

Bit 0: Channel 1 (0 = inhibited; 1 = enabled)
Bit 1: Channel 2
Bits 2 ... 7: Reserved

00

h

3

Reserved

0

1

0

Temperature system

Bit 0, 1: 00

b

= °C; 10

b

= °F; 11

b

= K

Bits 2 ... 7: Reserved

00

h

1

Interference
frequency suppression

Bit 0, 1: 01

b

= 60 Hz; 10

b

= 50 Hz

Bits 2 ... 7: Reserved

02

h

Channel 1

128

0

Function channel 1

176 (60

h

) ... 201 (C9

h

):

see "measuring range"

External temperature compensation: 176 (60

h

) ... 185

(69

h

)

Internal temperature compensation: 192 (C0

h

): ... 201

(C9

h

)

255 (FF

h

): channel deactivated

C1

h

1

Conversion time
channel 1

You can set the transformer speed as a function of the
interference frequency suppression (see 0x3105/x) for
each channel.
0 (00

h

): At 50 Hz: 324.1 ms/channel 16 bits; at 60 Hz:

270.5 ms/channel 16 bits
1 (01

h

): at 50 Hz: 164.2 ms/channel 16 bits; at 60 Hz:

137.2 ms/channel 16 bits
2 (02

h

): At 50 Hz: 84.2 ms/channel 16 bits; at 60 Hz:

70.5 ms/channel 16 bits
3 (03

h

): at 50 Hz: 44.1 ms/channel 16 bits; at 60 Hz:

37.2 ms/channel 16 bits
4 (04

h

): At 50 Hz: 24.2 ms/channel 16 bits; at 60 Hz:

20.5 ms/channel 16 bits
5 (05

h

): at 50 Hz: 14.2 ms/channel 16 bits; at 60 Hz:

12.2 ms/channel 16 bits
6 (06

h

): at 50 Hz: 9.2 ms/channel 16 bits; at 60 Hz:

8.0 ms/channel 16 bits
7 (07

h

): at 50 Hz: 6.6 ms/channel 15 bits; at 60 Hz:

5.9 ms/channel 15 bits
8 (08

h

): at 50 Hz: 4.2 ms/channel 13 bits; at 60 Hz:

3.8 ms/channel 13 bits

02

h

2, 3

Upper limit value
channel 1

You can define an upper or lower limit value for each
channel. For this you can only specify values from the
nominal range, otherwise you’ll receive a
parameterisation error. By specification of 7FFF

h

for the

upper or 8000

h

for the lower limit value, the

corresponding limit value is deactivated.
If the measured value is outside a limit value and the limit
value monitoring is activated, a process alarm is triggered.

7FFF

h

4, 5

Lower limit value
channel 1

8000

h