beautypg.com

14 "store" function, Canopen communication – Lenze I/O system 1000 System Manual User Manual

Page 340

background image

CANopen communication

"Store" function

8

l

340

EDSIO1000 EN 7.0

8.14

"Store" function

All parameter changes and the structure of the station are permanently stored via index
I1010

hex

(Store parameter).

)

Note!

If the real structure of the station does not correspond with its stored
structure anymore after a restart, the bus coupler module reports an error
(both red LEDs are blinking).
The stored structure of the station is deleted via index I1011

hex

(Restore

parameter).

Index

Name

Possible settings

Important

Lenze Selection

I1010

h

¿

Save All
Parameters

0

Saving the parameter settings
and the station structure in the
EEPPROM of the bus coupler.
Function in accordance with
CANopen (DS301/DS401
communication protocol).

^ 340

0

Number of subindexes assigned

Read only
Number of the subindexes used
by the index 1010

h

1 Save

0 = no function
1702257011

d

= save parameters

The numerical value is
ASCII−coded and complies with:
65 76 61 73

h

= "E" "V" "A" "S"