3 access to diagnostic data, Access to diagnostic data, Devicenet communication – Lenze I/O system 1000 System Manual User Manual
Page 562
DeviceNet communication
Access to the I/O system 1000
Access to diagnostic data
l
562
EDSIO1000 EN 7.0
11.2.3
Access to diagnostic data
The DeviceNet bus coupler exclusively supports passive diagnostics, i.e. no alarm
activation on the module side is required for diagnostics. You have to request the
diagnostics by yourself.
For this purpose, go to your configuration tool and select the diagnostic data of the
corresponding DeviceNet slot. All diagnostic data of the module will be displayed as byte
sequence.
DeviceNet bus coupler
Class code: 100 (64
h
)
No.
Name
Information
Format
Example
1
DeviceName
Device name
String
EPM−S150
2
HwVersion
HW output version
String
02
3
SwVersion
SW output version
String
V101
4
SerialNumber
Serial number
Unsigned16,
String
00000205
5
FpgaVersion
FPGA version
Unsigned16,
String
V208
6
MxFile
Mx file
String
MX000053.101
7
ProductVersion
Product version
String
01V01.00
8
OrderCode
Order no.
String
(8−digit Lenze material
number)
I/O compound module
Class code:
Slot 1: 101 (65
h
)
Slot 2: 102 (66
h
)
...
Slot 64: 164 (A4
h
)
No.
Name
Information
Format
Example
1
DeviceName
Device name
String
EPM−S403
2
HwVersion
HW output version
String
21
3
SwVersion
SW output version
String
V202
4
SerialNumber
Serial number
Unsigned32,
String
00001143
5
FpgaVersion
FPGA version
Unsigned16,
String
V208
6
MxFile
Mx file
String
MX000028.130
7
ProductVersion
Product version
String
01V31.001
8
OrderCode
Order no.
String
(8−digit Lenze material
number)
20
Parameter
Parameter data
String
x00 x00 x31 x31 x31 x31
21
Diagnostics
Diagnostic data
String
x00 x15 x00 x00
x73 x08 x04 x00
x00 x00 x00 x00
x00 x00 x00 x00
4x000020EB