beautypg.com

Product description – Lenze I/O system 1000 System Manual User Manual

Page 206

background image

Product description

I/O compound modules − counter
Two counters 32 bits, 24 V DC − EPM−S603

3

l

206

EDSIO1000 EN 7.0

Technical data

EPM−S603: rated data

Module identifier

2244

dec

Current consumption/power loss

Current consumption from backplane bus

75 mA

Power loss

0.9 W

Digital inputs

Number of inputs

4

Cable length

shielded

100 m

Load voltage

Nominal value

DC 20.4 ... 28.8 V

Current consumption from load voltage
L+

15 mA (without load)

Input voltage

Nominal value

DC 20.4 ... 28.8 V

for signal "0"

DC 0 ... 5 V

for signal "1"

DC 15 ... 28.8 V

Input current

for signal "1"

3 mA

2−wire BERO

Connection possible

Yes

Max. permissible closed−circuit current

0.5 mA

Input delay

from "0" to "1"

0.8

ms

from "1" to "0"

0.8

ms

Number of inputs which can be used simultaneously

horizontal structure

4

vertical structure

4

Input characteristic

IEC 61131, type 1

Input data size

12 bytes

Digital outputs

Output data size

4 bytes