EtherCAT Kommunikation
Parameterising technology modules
RS232 interface − EPM−S640
l
526
EDSIO1000 EN 7.0
Parameter data STX/ETX protocol
Lenze
Description/value
Name
Subindex
07
ZNA (HIGH byte)
Time delay after command; waiting time to be
complied with until the next transmit request is
executed.
0 ... 65535 [ms] (0000
h
.:. FFFF
h
)
0000
h
08
ZNA (LOW byte)
0000
h
09
TMO (HIGH byte)
TMO serves to define the maximally permissible
interval between two frames.
0 ... 65535 [ms] (0000
h
.:. FFFF
h
)
0Ah
0A
TMO (LOW byte)
0Ah
0B
No. of start identifiers
00
h
: 1 start identifier (2. start identifier is ignored)
01
h
: 2 start identifiers
01
h
0C
Start identifier 1
ASCII value of the initial character that is sent in
advance of a frame and marks the start of a
transmission.
1 ... 255 (01
h
... FF
h
)
02
h
0D
Start identifier 2
ASCII value of the initial character that is sent in
advance of a frame and marks the start of a
transmission.
00
h
0E
No. of end identifier
00
h
: 1 end identifier (2. end identifier (0x310D/x) is
ignored)
01
h
: 2 end identifiers
01
h
0F
End identifier 1
ASCII value of the end character that is sent after a
frame and marks the end of a transmission.
1 ... 255 (01
h
... FF
h
)
03
h
10
End identifier 2
ASCII value of the end character that is sent after a
frame and marks the end of a transmission.
1 ... 255 (01
h
... FF
h
)
00
h
11
Reserved