Product description, Technical data – Lenze I/O system 1000 System Manual User Manual
Page 158
![background image](/manuals/565636/158/background.png)
Product description
I/O compound modules − counter
One counter 32 bits, 24 V DC − EPM−S600
l
158
EDSIO1000 EN 7.0
Technical data
EPM−S600: rated data
Module identifier
2241
dec
Current consumption/power loss
Current consumption from backplane bus
75 mA
Power loss
1 W
Digital inputs
Number of inputs
5
Cable length
shielded
100 m
Load voltage
Nominal value
DC 20.4 ... 28.8 V
Current consumption from load voltage
L+
20 mA (without load)
Input voltage
Nominal value
DC 20.4 ... 28.8 V
for signal "0"
DC 0 ... 5 V
for signal "1"
DC 15 ... 28.8 V
Input current
for signal "1"
3 mA
2−wire BERO
Connection possible
Yes
Max. permissible closed−circuit current
0.5 mA
Input delay
from "0" to "1"
0.8
ms
from "1" to "0"
0.8
ms
Number of inputs which can be used simultaneously
horizontal structure
5
vertical structure
5
Input characteristic
IEC 61131, type 1
Input data size
12 bytes
Digital outputs
Number of outputs
1
Cable length
shielded
100 m
unshielded
100 m
Load voltage
Nominal value
DC 20.4 ... 28.8 V
Output delay
from "0" to "1"
30
ms
from "1" to "0"
30
ms
Lamp load
10 W
Parallel switching of outputs
for redundant control
Not possible
for power increase
Not possible
Control of a digital input
Possible