beautypg.com

Product description, Technical data – Lenze I/O system 1000 System Manual User Manual

Page 158

background image

Product description

I/O compound modules − counter
One counter 32 bits, 24 V DC − EPM−S600

3

l

158

EDSIO1000 EN 7.0

Technical data

EPM−S600: rated data

Module identifier

2241

dec

Current consumption/power loss

Current consumption from backplane bus

75 mA

Power loss

1 W

Digital inputs

Number of inputs

5

Cable length

shielded

100 m

Load voltage

Nominal value

DC 20.4 ... 28.8 V

Current consumption from load voltage
L+

20 mA (without load)

Input voltage

Nominal value

DC 20.4 ... 28.8 V

for signal "0"

DC 0 ... 5 V

for signal "1"

DC 15 ... 28.8 V

Input current

for signal "1"

3 mA

2−wire BERO

Connection possible

Yes

Max. permissible closed−circuit current

0.5 mA

Input delay

from "0" to "1"

0.8

ms

from "1" to "0"

0.8

ms

Number of inputs which can be used simultaneously

horizontal structure

5

vertical structure

5

Input characteristic

IEC 61131, type 1

Input data size

12 bytes

Digital outputs

Number of outputs

1

Cable length

shielded

100 m

unshielded

100 m

Load voltage

Nominal value

DC 20.4 ... 28.8 V

Output delay

from "0" to "1"

30

ms

from "1" to "0"

30

ms

Lamp load

10 W

Parallel switching of outputs

for redundant control

Not possible

for power increase

Not possible

Control of a digital input

Possible