Parameterising the temperature measurement
Four (two) analog inputs for resistance tests − EPM−S404

9

l

416

EDSIO1000 EN 7.0

9.6

Parameterising the temperature measurement

9.6.1

Four (two) analog inputs for resistance tests − EPM−S404

During the execution time you can access the parameter data via the following data sets:

Data set

Name

Description/value

Lenze

No.

Byte

0

0

Diagnostics

A diagnostic alarm occurs if the same event triggers a
further process alarm during a process alarm processing.
Bits 0 ... 5: Reserved
Bit 6: diagnostic alarm (0 = inhibited; 1 = enabled)
Bit 7: Reserved

00

h

1

Wire−breakage
detection

Bit 0: Channel 1 (0 = inhibited; 1 = enabled)
:
Bit 3: Channel 4
Bits 4 ... 7: Reserved

00

h

2

Limit value
monitoring

Bit 0: Channel 1 (0 = inhibited; 1 = enabled)
:
Bit 3: Channel 4
Bits 4 ... 7: Reserved

00

h

3

Reserved

1

0

Temperature system

Bit 0, 1: 00

b

= °C; 01

b

= °F; 10

b

= K

Bits 2 ... 7: Reserved

00

h

1

Interference
frequency suppression

Bit 0, 1: 01

b

= 60 Hz; 10

b

= 50 Hz

Bits 2 ... 7: Reserved

02

h

Channel 1

128

0

Function channel 1

80 (50

h

) ... 162 (A2

h

):

see "measuring range"

255 (FF

h

): channel deactivated

50

h

1

Conversion time
channel 1

You can set the transformer speed as a function of the
interference frequency suppression (see 0x3105/x) for
each channel.
0 (00

h

): At 50 Hz: 324.1 ms/channel 16 bits; at 60 Hz:

270.5 ms/channel 16 bits
1 (01

h

): At 50 Hz: 164.2 ms/channel 16 bits;

at 60 Hz: 137.2 ms/channel 16 bits
2 (02

h

): At 50 Hz: 84.2 ms/channel 16 bits;

at 60 Hz: 70.5 ms/channel 16 bits
3 (03

h

): at 50 Hz: 44.1 ms/channel 16 bits;

at 60 Hz: 37.2 ms/channel 16 bits
4 (04

h

): At 50 Hz: 24.2 ms/channel 16 bits;

at 60 Hz: 20.5 ms/channel 16 bits
5 (05

h

): At 50 Hz: 14.2 ms/channel 16 bits;

at 60 Hz: 12.2 ms/channel 16 bits
6 (06

h

): At 50 Hz: 9.2 ms/channel 16 bits;

at 60 Hz: 8.0 ms/channel 16 bits
7 (07

h

): At 50 Hz: 6.6 ms/channel 15 bits;

at 60 Hz: 5.9 ms/channel 15 bits
8 (08

h

): At 50 Hz: 4.2 ms/channel 13 bits;

at 60 Hz: 3.8 ms/channel 13 bits

00

h

2, 3

Upper limit value
channel 1

You can define an upper or lower limit value for each
channel. For this you can only specify values from the
nominal range, otherwise you’ll receive a
parameterisation error. By specification of 7FFF

h

for the

upper or 8000

h

for the lower limit value, the

corresponding limit value is deactivated. As soon as the
measured value is outside a limit value and limit value
monitoring is activated, a process alarm is triggered.

7FFF

h

4,5

Lower limit value
channel 1

8000

h