PROFIBUS communication
Parameterising the temperature measurement
Four (two) analog inputs for resistance tests − EPM−S404
l
416
EDSIO1000 EN 7.0
9.6
Parameterising the temperature measurement
9.6.1
Four (two) analog inputs for resistance tests − EPM−S404
During the execution time you can access the parameter data via the following data sets:
Data set
Name
Description/value
Lenze
No.
Byte
0
0
Diagnostics
A diagnostic alarm occurs if the same event triggers a
further process alarm during a process alarm processing.
Bits 0 ... 5: Reserved
Bit 6: diagnostic alarm (0 = inhibited; 1 = enabled)
Bit 7: Reserved
00
h
1
Wire−breakage
detection
Bit 0: Channel 1 (0 = inhibited; 1 = enabled)
:
Bit 3: Channel 4
Bits 4 ... 7: Reserved
00
h
2
Limit value
monitoring
Bit 0: Channel 1 (0 = inhibited; 1 = enabled)
:
Bit 3: Channel 4
Bits 4 ... 7: Reserved
00
h
3
Reserved
1
0
Temperature system
Bit 0, 1: 00
b
= °C; 01
b
= °F; 10
b
= K
Bits 2 ... 7: Reserved
00
h
1
Interference
frequency suppression
Bit 0, 1: 01
b
= 60 Hz; 10
b
= 50 Hz
Bits 2 ... 7: Reserved
02
h
Channel 1
128
0
Function channel 1
80 (50
h
) ... 162 (A2
h
):
see "measuring range"
255 (FF
h
): channel deactivated
50
h
1
Conversion time
channel 1
You can set the transformer speed as a function of the
interference frequency suppression (see 0x3105/x) for
each channel.
0 (00
h
): At 50 Hz: 324.1 ms/channel 16 bits; at 60 Hz:
270.5 ms/channel 16 bits
1 (01
h
): At 50 Hz: 164.2 ms/channel 16 bits;
at 60 Hz: 137.2 ms/channel 16 bits
2 (02
h
): At 50 Hz: 84.2 ms/channel 16 bits;
at 60 Hz: 70.5 ms/channel 16 bits
3 (03
h
): at 50 Hz: 44.1 ms/channel 16 bits;
at 60 Hz: 37.2 ms/channel 16 bits
4 (04
h
): At 50 Hz: 24.2 ms/channel 16 bits;
at 60 Hz: 20.5 ms/channel 16 bits
5 (05
h
): At 50 Hz: 14.2 ms/channel 16 bits;
at 60 Hz: 12.2 ms/channel 16 bits
6 (06
h
): At 50 Hz: 9.2 ms/channel 16 bits;
at 60 Hz: 8.0 ms/channel 16 bits
7 (07
h
): At 50 Hz: 6.6 ms/channel 15 bits;
at 60 Hz: 5.9 ms/channel 15 bits
8 (08
h
): At 50 Hz: 4.2 ms/channel 13 bits;
at 60 Hz: 3.8 ms/channel 13 bits
00
h
2, 3
Upper limit value
channel 1
You can define an upper or lower limit value for each
channel. For this you can only specify values from the
nominal range, otherwise you’ll receive a
parameterisation error. By specification of 7FFF
h
for the
upper or 8000
h
for the lower limit value, the
corresponding limit value is deactivated. As soon as the
measured value is outside a limit value and limit value
monitoring is activated, a process alarm is triggered.
7FFF
h
4,5
Lower limit value
channel 1
8000
h