EtherCAT Kommunikation

Parameterising the temperature measurement
Four (two) analog inputs for resistance tests − EPM−S404

10

l

500

EDSIO1000 EN 7.0

Lenze

Description/value

Name

Subindex

08

Conversion time
channel 1

You can set the transformer speed as a function of the
interference frequency suppression (see 0x3105/x) for each
channel.
0 (00

h

): At 50 Hz: 324.1 ms/channel 16 bits; at 60 Hz:

270.5 ms/channel 16 bits
1 (01

h

): At 50 Hz: 164.2 ms/channel 16 bits;

at 60 Hz: 137.2 ms/channel 16 bits
2 (02

h

): At 50 Hz: 84.2 ms/channel 16 bits;

at 60 Hz: 70.5 ms/channel 16 bits
3 (03

h

): at 50 Hz: 44.1 ms/channel 16 bits;

at 60 Hz: 37.2 ms/channel 16 bits
4 (04

h

): At 50 Hz: 24.2 ms/channel 16 bits;

at 60 Hz: 20.5 ms/channel 16 bits
5 (05

h

): At 50 Hz: 14.2 ms/channel 16 bits;

at 60 Hz: 12.2 ms/channel 16 bits
6 (06

h

): At 50 Hz: 9.2 ms/channel 16 bits;

at 60 Hz: 8.0 ms/channel 16 bits
7 (07

h

): At 50 Hz: 6.6 ms/channel 15 bits;

at 60 Hz: 5.9 ms/channel 15 bits
8 (08

h

): At 50 Hz: 4.2 ms/channel 13 bits;

at 60 Hz: 3.8 ms/channel 13 bits

00

h

09

Upper limit value
channel 1

You can define an upper or lower limit value for each channel.
For this you can only specify values from the nominal range,
otherwise you’ll receive a parameterisation error. By
specification of 7FFFh for the upper or 8000h for the lower limit
value, the corresponding limit value is deactivated.
If your measured value is outside a limit value and you have
activated the limit value monitoring, a process alarm is
triggered.

7FFF

h

0A

Lower limit value
channel 1

8000

h

Channel 2

0B

Function channel 2

See channel 1

50

h

0C

Conversion time
channel 2

See channel 1

00

h

0D

Upper limit value
channel 2

See channel 1

7FFF

h

0E

Lower limit value
channel 2

8000

h

Channel 3 (for two−wire conductor connections only)

0F

Function channel 3

See channel 1

50

h

10

Conversion time
channel 3

See channel 1

00

h

11

Upper limit value
channel 3

See channel 1

7FFF

h

12

Lower limit value
channel 3

8000

h