beautypg.com

Product description, Technical data – Lenze I/O system 1000 System Manual User Manual

Page 141

background image

Product description

I/O compound modules − analog I/O

2 analog outputs 0/4 ... 20 mA (12 bits) − EPM−S502

3

l

141

EDSIO1000 EN 7.0

Technical data

EPM−S502: Rated data

Module identifier

1282

dec

Current consumption/power loss

Current consumption from backplane bus

80 mA

Power loss

0.8 W

Analog outputs

Number of outputs

2

Cable length

shielded

200 m

Load voltage

Nominal value

DC 24 V

Current consumpt. from load voltage L+

15 mA (without load)

Current outputs

Output current ranges

0 mA ... +20 mA
+4 mA ... +20 mA

Max. load impedance

350

W

Max. inductive load

10 mH

Operational error limit

+/− 0.4 % ... +/− 0.5 %

Basic error limit

+/− 0.2 % ... +/− 0.3 %

Short circuit protection

No

Voltage at the outputs

12 V

Interference suppression (cross−talk
between the outputs)

> 40 dB

Resolution

12 bits

Basic conversion time

2 ms all channels

Substitute values can be applied

Yes

Temperature error
(relating to the output range)

± 0.01 %/K

Linearity distortion
(relating to the output range)

± 0.1 %

Output ripple; bandwidth 0 to 50 kHz
(relating to the output range)

± 0.05 %

Repeat accuracy (in steady−state vibration at
25°C, relating to the output range)

± 0.05 %

Dwell time

for ohmic loads

0.25 ms

for inductive load

1.5 ms

Output data size

4 bytes

Status, alarm, diagnostics

Status display

Yes

Alarms

No

Process alarm

No

Diagnostic alarm

No

Diagnostic function

Yes

Diagnostic information can be read out

Possible

Module status

Green LED

Module error display

Red LED

Channel error display

Red LEDs per channel