2 analog inputs −10 ... +10 v (16 bits) − epm−s406, Devicenet communication – Lenze I/O system 1000 System Manual User Manual
Page 567

DeviceNet communication
Setting the parameters of analog I/O
2 analog inputs −10 ... +10 V (16 bits) − EPM−S406
l
567
EDSIO1000 EN 7.0
11.3.5
2 analog inputs −10 ... +10 V (16 bits) − EPM−S406
Parameter data
Pos. in
string of
digits
Name
Description/value
Lenze
1
Diagnostics
Bits 0 ... 5: Reserved
Bit 6: Diagnostic alarm (0 = inhibited; 1 = enabled)
Bit 7: Reserved
00
h
2
Reserved
0
3
Limit value
monitoring
Bit 0: Channel 1 (0 = deactivated; 1 = activated)
Bit 1: Channel 2 (0 = deactivated; 1 = activated)
Bits 7 ... 2: Reserved
00
h
4
Interference
frequency
suppression
Bit 1, 0: Channel 1
00: Deactivated
01: 60 Hz
10: 50 Hz
Bit 3, 2: Channel 2
00: Deactivated
01: 60 Hz
10: 50 Hz
Bits 7 ... 4: Reserved
00
h
5
Function channel 1
12 (12
h
): −10 ... 10 V / −27648 ... 27648
dec
34 (22
h
): −10 ... 10 V / −16384 ... 16384
dec
16 (10
h
): 0 ... 10 V / 0 ... 27648
dec
32 (20
h
): 0 ... 10 V / 0 ... 16384
dec
255 (FF
h
): channel deactivated
20
h
6
Reserved
0
7
Upper limit value
channel 1
Value from the rated range; if this value is exceeded and the
limit value monitoring function is active, a process alarm is
triggered.
7FFF
h
: Limit value alarm deactivated
7FFF
h
8
Lower limit value
channel 1
Value from the rated range; if the actual value falls below this
value and the limit value monitoring function is active, a process
alarm is triggered.
8000
h
: Limit value alarm deactivated
8000
h
9
Function channel 2
12 (12
h
): −10 ... 10 V / −27648 ... 27648
dec
34 (22
h
): −10 ... 10 V / −16384 ... 16384
dec
16 (10
h
): 0 ... 10 V / 0 ... 27648
dec
32 (20
h
): 0 ... 10 V / 0 ... 16384
dec
255 (FF
h
): channel deactivated
20
h
10
Reserved
0
11
Upper limit value
channel 2
Value from the rated range; if this value is exceeded and the
limit value monitoring function is active, a process alarm is
triggered.
7FFF
h
: Limit value alarm deactivated
7FFF
h
12
Lower limit value
channel 2
Value from the rated range; if the actual value falls below this
value and the limit value monitoring function is active, a process
alarm is triggered.
8000
h
: Limit value alarm deactivated
8000
h
With the formulas listed in the following you can convert a digital value into an analog
output value and vice versa.