beautypg.com

2 analog inputs −10 ... +10 v (16 bits) − epm−s406, Devicenet communication – Lenze I/O system 1000 System Manual User Manual

Page 567

background image

DeviceNet communication

Setting the parameters of analog I/O

2 analog inputs −10 ... +10 V (16 bits) − EPM−S406

11

l

567

EDSIO1000 EN 7.0

11.3.5

2 analog inputs −10 ... +10 V (16 bits) − EPM−S406

Parameter data

Pos. in
string of
digits

Name

Description/value

Lenze

1

Diagnostics

Bits 0 ... 5: Reserved
Bit 6: Diagnostic alarm (0 = inhibited; 1 = enabled)
Bit 7: Reserved

00

h

2

Reserved

0

3

Limit value
monitoring

Bit 0: Channel 1 (0 = deactivated; 1 = activated)
Bit 1: Channel 2 (0 = deactivated; 1 = activated)
Bits 7 ... 2: Reserved

00

h

4

Interference
frequency
suppression

Bit 1, 0: Channel 1

00: Deactivated
01: 60 Hz
10: 50 Hz

Bit 3, 2: Channel 2

00: Deactivated
01: 60 Hz
10: 50 Hz

Bits 7 ... 4: Reserved

00

h

5

Function channel 1

12 (12

h

): −10 ... 10 V / −27648 ... 27648

dec

34 (22

h

): −10 ... 10 V / −16384 ... 16384

dec

16 (10

h

): 0 ... 10 V / 0 ... 27648

dec

32 (20

h

): 0 ... 10 V / 0 ... 16384

dec

255 (FF

h

): channel deactivated

20

h

6

Reserved

0

7

Upper limit value
channel 1

Value from the rated range; if this value is exceeded and the
limit value monitoring function is active, a process alarm is
triggered.
7FFF

h

: Limit value alarm deactivated

7FFF

h

8

Lower limit value
channel 1

Value from the rated range; if the actual value falls below this
value and the limit value monitoring function is active, a process
alarm is triggered.
8000

h

: Limit value alarm deactivated

8000

h

9

Function channel 2

12 (12

h

): −10 ... 10 V / −27648 ... 27648

dec

34 (22

h

): −10 ... 10 V / −16384 ... 16384

dec

16 (10

h

): 0 ... 10 V / 0 ... 27648

dec

32 (20

h

): 0 ... 10 V / 0 ... 16384

dec

255 (FF

h

): channel deactivated

20

h

10

Reserved

0

11

Upper limit value
channel 2

Value from the rated range; if this value is exceeded and the
limit value monitoring function is active, a process alarm is
triggered.
7FFF

h

: Limit value alarm deactivated

7FFF

h

12

Lower limit value
channel 2

Value from the rated range; if the actual value falls below this
value and the limit value monitoring function is active, a process
alarm is triggered.
8000

h

: Limit value alarm deactivated

8000

h

With the formulas listed in the following you can convert a digital value into an analog
output value and vice versa.