beautypg.com

Devicenet communication – Lenze I/O system 1000 System Manual User Manual

Page 606

background image

DeviceNet communication

Parameterising technology modules
RS232 interface − EPM−S640

11

l

606

EDSIO1000 EN 7.0

Parameter data 3964(R) protocol

Lenze

Description/value

Name

Pos. in
string of
digits

8

Character delay time

Character delay time; the character delay time defines
the max. permissible interval between two received
characters within a frame. If the character delay time is
0, the module independently calculates the character
delay time on the basis of the baud rate (approx. the
double character time).
0 ... 65535 [20−ms steps] (00

h

.:. FF

h

)

0Ah

9

Acknowledgement time

The acknowledgement time defines the max.
permissible interval until the partner is acknowledged
while establishing/terminating a connection.
0 ... 65535 [20−ms steps] (00

h

.:. FF

h

)

0A

h

10

Block wait time

Maximum time between the recognition of a
requested frame (DLE) and the response.
0 ... 255 [ms] (00

h

... FF

h

)

0A

h

11

STX repetitions

Maximum number of times the EPM−S640 tries to
establish a connection.
0 ... 255 [ms] (00

h

... FF

h

)

05

h

12

DBL

If the block wait time has been exceeded, the number
of STX repetitions for the requested protocol can be
specified here.
0 ... 255 [ms] (00

h

... FF

h

)

06

h

13

Priority

A communication partner has high priority if the
transmission attempt has priority over the partner’s
request to transmit. With a low priority, the partner’s
request to transmit comes first. In case of the protocols
3964(R), both partners must have different priorities.
00

h

: LOW

01

h

: HIGH

00

h