Product description

I/O compound modules − temperature measurement

Four (two) analog inputs for resistance tests − EPM−S404

3

l

151

EDSIO1000 EN 7.0

EPM−S404: Rated data

Electrical isolation

Between the channels and the backplane
bus

Yes

Between the channels and the voltage
supply

Yes

Max. potential difference between inputs
(U

cm

)

DC 6 V

Max. potential difference between inputs
and M

internal

(U

iso

)

DC 75 V / AC 60 V

Insulation checked with