beautypg.com

Product description, Technical data – Lenze I/O system 1000 System Manual User Manual

Page 81

background image

Product description

I/O compound modules − digital I/O

2 digital inputs with time stamp function − EPM−S207

3

l

81

EDSIO1000 EN 7.0

Technical data

EPM−S207: rated data

Module identifier

3841

dec

Current consumption/power loss

Current consumption from backplane bus

85 mA

Power loss

0.9 W

Digital inputs

Number of inputs

2

Cable length

shielded

1000 m

unshielded

600 m

Load voltage

Nominal value

DC 24 V

Current consumption from load voltage
L+

10 mA (without load)

Input voltage

Nominal value

DC 20.4 ... 28.8 V

for signal "0"

DC 0 ... 5 V

for signal "1"

DC 15 ... 28.8 V

Input current

for signal "1"

3 mA

2−wire BERO

Connection possible

Yes

Max. permissible closed−circuit current

0.5 mA

Input delay

from "0" to "1"

Parameterisable

from "1" to "0"

Parameterisable

Number of inputs which can be used simultaneously

horizontal structure

2

vertical structure

2

Input characteristic

IEC 61131, type 1

Input data size

60 bytes

Status, alarm, diagnostics

Status display

Green LEDs per channel

Alarms

No

Process alarm

No

Diagnostic alarm

No

Diagnostic function

No

Diagnostic information can be read out

Possible

Module status

Green LED

Module error display

Red LED

Channel error display

None

Electrical isolation

zwischen Kanälen in Gruppen zu

2

Between the channels and the backplane
bus

Yes

Insulation checked with

DC 500 V