Product description, Technical data – Lenze I/O system 1000 System Manual User Manual
Page 81
Product description
I/O compound modules − digital I/O
2 digital inputs with time stamp function − EPM−S207
l
81
EDSIO1000 EN 7.0
Technical data
EPM−S207: rated data
Module identifier
3841
dec
Current consumption/power loss
Current consumption from backplane bus
85 mA
Power loss
0.9 W
Digital inputs
Number of inputs
2
Cable length
shielded
1000 m
unshielded
600 m
Load voltage
Nominal value
DC 24 V
Current consumption from load voltage
L+
10 mA (without load)
Input voltage
Nominal value
DC 20.4 ... 28.8 V
for signal "0"
DC 0 ... 5 V
for signal "1"
DC 15 ... 28.8 V
Input current
for signal "1"
3 mA
2−wire BERO
Connection possible
Yes
Max. permissible closed−circuit current
0.5 mA
Input delay
from "0" to "1"
Parameterisable
from "1" to "0"
Parameterisable
Number of inputs which can be used simultaneously
horizontal structure
2
vertical structure
2
Input characteristic
IEC 61131, type 1
Input data size
60 bytes
Status, alarm, diagnostics
Status display
Green LEDs per channel
Alarms
No
Process alarm
No
Diagnostic alarm
No
Diagnostic function
No
Diagnostic information can be read out
Possible
Module status
Green LED
Module error display
Red LED
Channel error display
None
Electrical isolation
zwischen Kanälen in Gruppen zu
2
Between the channels and the backplane
bus
Yes
Insulation checked with
DC 500 V