Parameterising the temperature measurement

Two analog inputs for thermocouple measurement − EPM−S405

8

l

307

EDSIO1000 EN 7.0

Lenze

Description/value

Name

Index/sub
index

0x3107/x Conversion time

channel 1

You can set the transformer speed as a function of the
interference frequency suppression (see 0x3105/x) for each
channel.
0 (00

h

): At 50 Hz: 324.1 ms/channel 16 bits; at 60 Hz:

270.5 ms/channel 16 bits
1 (01

h

): at 50 Hz: 164.2 ms/channel 16 bits; at 60 Hz:

137.2 ms/channel 16 bits
2 (02

h

): At 50 Hz: 84.2 ms/channel 16 bits; at 60 Hz:

70.5 ms/channel 16 bits
3 (03

h

): at 50 Hz: 44.1 ms/channel 16 bits; at 60 Hz:

37.2 ms/channel 16 bits
4 (04

h

): At 50 Hz: 24.2 ms/channel 16 bits; at 60 Hz:

20.5 ms/channel 16 bits
5 (05

h

): at 50 Hz: 14.2 ms/channel 16 bits; at 60 Hz:

12.2 ms/channel 16 bits
6 (06

h

): at 50 Hz: 9.2 ms/channel 16 bits; at 60 Hz:

8.0 ms/channel 16 bits
7 (07

h

): at 50 Hz: 6.6 ms/channel 15 bits; at 60 Hz:

5.9 ms/channel 15 bits
8 (08

h

): at 50 Hz: 4.2 ms/channel 13 bits; at 60 Hz:

3.8 ms/channel 13 bits

02

h

0x3108/x Upper limit value

(HIGH byte) channel 1 You can define an upper or lower limit value for each channel.

For this you can only specify values from the nominal range,
otherwise you’ll receive a parameterisation error. By
specification of 7FFFh for the upper or 8000h for the lower limit
value, the corresponding limit value is deactivated.
If your measured value is outside a limit value and you have
activated the limit value monitoring, a process alarm is
triggered.

7F

h

0x3109/x Upper limit value

channel 1 (LOW byte)

FF

h

0x310A/x Lower limit value

(HIGH byte) channel 1

80

h

0x310B/x Lower limit value

channel 1 (LOW byte)

00

h

Channel 2

0x310C/x Function channel 2

See channel 1

C1

h

0x310D/x Conversion time

channel 2

See channel 1

02

h

0x310E/x Upper limit value

channel 2 (HIGH byte)

7F

h

0x310F/x

Upper limit value
(LOW byte) channel 2

FF

h

0x3110/x Lower limit value

channel 2 (HIGH byte)

80

h

0x3111/x Lower limit value

(LOW byte) channel 2

00

h

0x3112/x Reserved

0

...

...

...

0x311D/x Reserved

0