Devicenet communication – Lenze I/O system 1000 System Manual User Manual

Page 570

background image

DeviceNet communication

Setting the parameters of analog I/O
2 analog inputs 0/4 ... 20 mA (16 bits) − EPM−S408

11

l

570

EDSIO1000 EN 7.0

Measuring range

Current (I)

Decimal (D)

Hex

Range

Conversion

(Fct. no.)

[mA]

0 ... 20 mA

(31

h

)

23.52

32511

7EFF

Overflow

I = D * 20 / 27648
D = 27648 * I / 20

20

27648

6C00

Nominal range

10

13824

3600

0

0

0000

−3.52

−4864

ED00

Underflow

0 ... 20 mA

(41

h

)

25

20480

5000

Overflow

I = D * 20 / 16384
D = 16384 * I / 20

20

16384

4000

Nominal range

10

8192

2000

0

0

0000

−4

−3277

F333

Underflow

4 ... 20 mA

(30

h

)

22.81

32511

7EFF

Overflow

I = D * 16 / 27648 + 4

D = 27648 * (I−4) / 16

20

27648

6C00

Nominal range

12

13824

3600

4

0

0000

1,19

−4864

ED00

Underflow

4 ... 20 mA

(40

h

)

24

20480

5000

Overflow

I = D * 16 / 16384 + 4

D = 16384 * (I−4) / 16

20

16384

4000

Nominal range

12

8192

2000

4

0

0000

0.8

−3277

F333

Underflow