Product description, Status displays, Terminals – Lenze I/O system 1000 System Manual User Manual

Page 144: Outputs that are not used are not connected

background image

Product description

I/O compound modules − analog I/O
4 analog outputs 0/4 ... 20 mA (12 bits) − EPM−S503

3

l

144

EDSIO1000 EN 7.0

Status displays

Module status LEDs

0

View

Pos.

Designation

Colour

Explanation

1

10

1

RUN

Green

On: Module is ready for operation

2

MF

Red

On: Module error (see table below)

3

AO1

Red

On: Channel 1, open circuit, parameterisation error

4

AO2

Red

On: Channel 2, open circuit, parameterisation error

5

AO3

Red

On: Channel 3, open circuit, parameterisation error

6

AO4

Red

On: Channel 4, open circuit, parameterisation error

7

Not assigned

8

9

SLIO001

10

Messages of the status LEDs RUN and MF

RUN

MF

Meaning

On

Off

Module status OK
Bus communication is OK

On

On

Module reports error
Bus communication is OK

Off

On

Module reports error
Bus communication not possible

Off

Off

Error in the bus supply voltage

Blinking

Blinking

Configuration error (

^ 249)

Terminals

Module terminals, spring terminals

1

View

Designation

Explanation

Terminal data

2

6

3

7

4

8

1

5

1

5

4

8

1

Analog output AO1 (+)

10 mm

0.08 ... 1.5 mm²

(AWG 28 ... 16)

2

Analog output AO1 (GND)

3

Analog output AO3 (+)

4

Analog output AO3 (GND)

5

Analog output AO2 (+)

6

Analog output AO2 (GND)

7

Analog output AO4 (+)

SLIO002

8

Analog output AO4 (GND)

)

Note!

ƒ

When connecting the actuators, make sure that the polarity is correct.

ƒ

Outputs that are not used are not connected.

ƒ

The module does not provide any auxiliary supply for actuators.