Product description, Status displays, Terminals – Lenze I/O system 1000 System Manual User Manual
Page 144: Outputs that are not used are not connected
Product description
I/O compound modules − analog I/O
4 analog outputs 0/4 ... 20 mA (12 bits) − EPM−S503
l
144
EDSIO1000 EN 7.0
Status displays
Module status LEDs
0
View
Pos.
Designation
Colour
Explanation
1
10
1
RUN
Green
On: Module is ready for operation
2
MF
Red
On: Module error (see table below)
3
AO1
Red
On: Channel 1, open circuit, parameterisation error
4
AO2
Red
On: Channel 2, open circuit, parameterisation error
5
AO3
Red
On: Channel 3, open circuit, parameterisation error
6
AO4
Red
On: Channel 4, open circuit, parameterisation error
7
−
−
Not assigned
8
9
SLIO001
10
Messages of the status LEDs RUN and MF
RUN
MF
Meaning
On
Off
Module status OK
Bus communication is OK
On
On
Module reports error
Bus communication is OK
Off
On
Module reports error
Bus communication not possible
Off
Off
Error in the bus supply voltage
Blinking
Blinking
Configuration error (
^ 249)
Terminals
Module terminals, spring terminals
1
View
Designation
Explanation
Terminal data
2
6
3
7
4
8
1
5
1
5
4
8
1
Analog output AO1 (+)
10 mm
0.08 ... 1.5 mm²
(AWG 28 ... 16)
2
Analog output AO1 (GND)
3
Analog output AO3 (+)
4
Analog output AO3 (GND)
5
Analog output AO2 (+)
6
Analog output AO2 (GND)
7
Analog output AO4 (+)
SLIO002
8
Analog output AO4 (GND)
)
Note!
ƒ
When connecting the actuators, make sure that the polarity is correct.
ƒ
Outputs that are not used are not connected.
ƒ
The module does not provide any auxiliary supply for actuators.