DeviceNet communication

Parameterising the temperature measurement
Two analog inputs for thermocouple measurement − EPM−S405

11

l

582

EDSIO1000 EN 7.0

Lenze

Description/value

Name

Pos. in
string of
digits

08

Conversion time
channel 1

You can set the transformer speed as a function of the
interference frequency suppression (see 0x3105/x) for each
channel.
0 (00

h

): At 50 Hz: 324.1 ms/channel 16 bits; at 60 Hz:

270.5 ms/channel 16 bits
1 (01

h

): at 50 Hz: 164.2 ms/channel 16 bits; at 60 Hz:

137.2 ms/channel 16 bits
2 (02

h

): At 50 Hz: 84.2 ms/channel 16 bits; at 60 Hz:

70.5 ms/channel 16 bits
3 (03

h

): at 50 Hz: 44.1 ms/channel 16 bits; at 60 Hz:

37.2 ms/channel 16 bits
4 (04

h

): At 50 Hz: 24.2 ms/channel 16 bits; at 60 Hz:

20.5 ms/channel 16 bits
5 (05

h

): at 50 Hz: 14.2 ms/channel 16 bits; at 60 Hz:

12.2 ms/channel 16 bits
6 (06

h

): at 50 Hz: 9.2 ms/channel 16 bits; at 60 Hz:

8.0 ms/channel 16 bits
7 (07

h

): at 50 Hz: 6.6 ms/channel 15 bits; at 60 Hz:

5.9 ms/channel 15 bits
8 (08

h

): at 50 Hz: 4.2 ms/channel 13 bits; at 60 Hz:

3.8 ms/channel 13 bits

02

h

09

Upper limit value
channel 1

You can define an upper or lower limit value for each channel.
For this you can only specify values from the nominal range,
otherwise you’ll receive a parameterisation error. By
specification of 7FFFh for the upper or 8000h for the lower limit
value, the corresponding limit value is deactivated.
If your measured value is outside a limit value and you have
activated the limit value monitoring, a process alarm is
triggered.

7FFF

h

0A

Lower limit value
channel 1

8000

h

Channel 2

0B

Function channel 2

See channel 1

C1

h

0C

Conversion time
channel 2

See channel 1

02

h

0D

Upper limit value
channel 2

See channel 1

7FFF

h

0E

Lower limit value
channel 2

8000

h

Measuring range

Measuring range

Measured value

Range

(Fct. no.)

[°C]

[°F]

[K]

Type J:

−210 ... +1200 °C

−346 ... 2192 °F

63.2 ... 1473.2 K

(B0

h

: ext. comp. 0 °C)

(C0

h

: int. comp. 0 °C)

+14500

26420

17232

Overflow

−2100 ... +12000

−3460 ... +21920

632 ... 14732

Nominal range

Underflow

Type K:

−210 ... +1372 °C

−454 ... 2501.6 °F

0 ... 1645.2 K

(B1

h

: ext. comp. 0 °C)

(C1

h

: int. comp. 0 °C)

+16220

29516

18952

Overflow

−2700 ... +13720

−4540 ... 25016

0 ... 16452

Nominal range

Underflow