beautypg.com

Computers using rpx (rp−0000) protocol – Grass Valley VM 3000 System Controllers v.7.4 User Manual

Page 339

background image

Configurator

MPK Devices

5−129

VM 3000 Installation and Operating Manual

COMPUTERS USING RPX (RP−0000) PROTOCOL

Hardware installation was discussed on page 2−86; serial port configuration was discussed on page 5−25. Figure 5−104 shows
an example table for the system shown on page 2−86.

SWITCHPC

Serial

SI3

8

PC−INP

PC−OUT

1

MPK Devices

MPK

Expansion

Pass

Board

Port

Address

Input Sets

Output Sets

Level Set

Overide Set

Sequence Set

2

KXYZ−LEV

Devices

word

In Panel

Out Panel

00000001

Device

Type

Figure 5−104. Entry for system shown on page 2−86.

For Device Type, select “Serial.”

The Address field contains the “site number” of the controlling computer. The site number, which is defined by the end−user,
must be a number from 0x01 to 0x7F hex (1−127 decimal). For example, if the site number is 16 decimal then “00000010”
must be entered into this field; if the site number is 15 decimal then “0000000F” must be entered into this field (see Appendix
D for a decimal−to−hexadecimal chart).

The Input, Output, and Level sets named on this table should include all inputs, outputs, and levels that will be controlled
by the external control computer. As a precaution, you may wish to restrict computer control to selected outputs.

The Input (page 5−58) and Output (page 5−76) sets must be created specifically for use by “serial” devices.

The Level Set must be created as a type “CP 3000” (see page 5−55.) For an important note about level numbering and external
computer control, see page 5−57.

A technical description of the RPX computer interface protocol is available on request.

This manual is related to the following products: