Data switching − off time between switches, Switchers, leave blank – Grass Valley VM 3000 System Controllers v.7.4 User Manual
Page 253

Configurator
Switcher Description Table
5−43
VM 3000 Installation and Operating Manual
DM 400 Off Time
DATA SWITCHING − OFF TIME BETWEEN SWITCHES
Number of frames switcher will dwell on Safe input when switching between controlled devices
When a switch occurs from one VTR control cable to another where the VTRs are of different types, the switch can occur
so rapidly that the editing system may not know that a new type of VTR has been connected. This can result in editing
inaccuracies since the editing system may be using ballistics for the wrong type of VTR. See Figure 5−27.
Figure 5−27.
Editor
VTR 1
VTR 2
Data Switcher
“Safe input”
To avoid this problem, the data switcher can be set to switch to a Safe input, wait for a specified minimum number of frames,
and then switch to the new device. This will cause the editing system to send a request to the new VTR to identify itself and
get the correct ballistics.
The wait period is set in the “DM 400 Off Time” column of the Switcher Description table. A setting of approximately 3/4
second is recommended (20 frames). The maximum value is 99 frames.
The DM 400A data switcher requires a two−row entry on the Switcher Description table; in this case the DM 400 Off Time
entry is made on the Reverse switcher row (the row with the letter “R” in the RV column).