3 general synchronous operation guidelines, 1 address multiplexing, 3 general synchronous operation guidelines -9 – Motorola ColdFire MCF5281 User Manual
Page 281: 1 address multiplexing -9
Synchronous DRAM Controller Module
Freescale Semiconductor
15-9
15.2.3
General Synchronous Operation Guidelines
To reduce system logic and to support a variety of SDRAM sizes, the DRAM controller provides SDRAM
control signals as well as a multiplexed row address and column address to the SDRAM.
15.2.3.1
Address Multiplexing
shows the generic address multiplexing scheme for SDRAM configurations. All possible
address connection configurations can be derived from this table.
NOTE
Because the processor has 24 extermal address lines, the maximum
SDRAM address size is 128 Mbits.
The following tables provide a more comprehensive, step-by-step way to determine the correct address
line connections for interfacing the ColdFire processor to the SDRAM. To use the tables, find the one that
corresponds to the number of column address lines on the SDRAM and to the port size as seen by the
processor, which is not necessarily the SDRAM port size. For example, if two 1M x 16-bit SDRAMs
together form a 1M x 32-bit memory, the port size is 32 bits. Most SDRAMs likely have fewer address
lines than are shown in the tables, so follow only the connections shown until all SDRAM address lines
are connected.
Table 15-7. Generic Address Multiplexing Scheme
Address Pin
Row Address
Column Address
Notes Relating to Port Sizes
17
17
0
8-bit port only
16
16
1
8- and 16-bit ports only
15
15
2
14
14
3
13
13
4
12
12
5
11
11
6
10
10
7
9
9
8
17
17
16 32-bit
port
only
18
18
17
16-bit port only or 32-bit port with only 8 column address lines
19
19
18
16-bit port only when at least 9 column address lines are used
20
20
19
21
21
20
22
22
21
23
23
22
MCF5282 and MCF5216 ColdFire Microcontroller User’s Manual, Rev. 3