Table 2-1 Environmental Requirements
Requirement
Operating
Non-operating
Temperature
+5 ºC (+41 °F) to +40 ºC
(+104 °F) (normal operation)
according to NEBS Standard
GR- 63-CORE
-5 ºC (+23 °F) to +55 ºC (+131
°F) (exceptional operation)
according to NEBS Standard
GR-63-CORE
-40 ºC (-40 °F) to +70 ºC (+158 °F)
Airflow
The blade is designed to
operate in a chassis that
provides B4 cooling per CP-
TA
Temp. change
+/- 0.25 ºC/min according to
NEBS Standard GR-63-CORE
+/- 0.25 ºC/min
Rel. humidity
5% to 90% non-condensing
5% to 95% non-condensing
Vibration
20 to 2000Hz
0.1 g from 5 to 100 Hz (Rack
Level according to NEBS
Standard GR-63-CORE)
5-20 Hz at 0.01 g2/Hz
20-200 Hz at -3.0 dB/octave
Random 5-20 Hz at 1 m2/Sec3
Random 20-200 Hz at -3 m/Sec2