Fabric OS Message Reference
53-1001767-01
TS-1006
104
TS-1006
Message
Probable Cause
Indicates a time service event is occurring or has failed. The message might be one of the
following:
•
Init failed. Time Service exiting
Probable Cause: Initialization error, Time Server exits.
•
Synchronizing time of day clock
Probable Cause: Usually logged during temporary operational issues when the clock goes out
of synchronization: For example, when a time update packet is missed due to fabric
reconfiguration or role change of the principal or primary fabric configuration server (FCS)
switch. If the message does not recur, it should be ignored.
•
Validating time update
Probable Cause: Usually logged during temporary operational issues when a time update
packet cannot be validated in a secure fabric. For example, during fabric reconfiguration or role
change of the primary FCS switch. If the message does not recur, it should be ignored.
Recommended
Action
No action is required.
Severity
INFO
TS-1007
Message
Probable Cause
Indicates a switch is trying to set the tsclockserver, which is not the primary fabric configuration
server (FCS) across the fabric. A consistent FCS policy must be implemented across the fabric.
Recommended
Action
Verify the FCS policy is consistent across the fabriclog_ts.xml.
Severity
WARNING
TS-1008
Message
server used> Clock Server used instead of Probable Cause Indicates there is a change in the source of fabric time synchronization distributed from the Recommended Action No action is required. Severity WARNING
principal or primary fabric configuration server (FCS) switch. Another clock server in the list of clock
servers configured is being used. This happens when the network time protocol (NTP) query to the
current active external clock server fails.