Hil-1502, Hil-1503, Hil-1504 – Dell POWEREDGE M1000E User Manual
Page 454

378
Fabric OS Message Reference
53-1001767-01
HIL-1502
45
Recommended
Action
Run the fanShow command to verify all the fans are working properly.
Make sure that the area is well-ventilated and that the room temperature is within operational
range of your switch. Refer to the hardware reference manual for your switch for the operational
temperature range.
Severity
WARNING
HIL-1502
Message
in 2 minutes if temperature remains high.
Probable Cause
Indicates that the temperature of this blade has risen above the critical threshold. This usually
follows a high-temperature message.
Recommended
Action
Run the fanShow command to verify all the fans are working properly.
Make sure that the area is well-ventilated and that the room temperature is within operational
range of your switch. Refer to the hardware reference manual for your switch for the operational
temperature range.
If the message persists, replace the blade.
Severity
CRITICAL
HIL-1503
Message
<
slot number
>
, unit shutting down.
Probable Cause
Indicates that the temperature of this blade has been above the maximum threshold for at least
two minutes. The blade is shut down to prevent damage. This usually follows a high-temperature
warning message.
Recommended
Action
Run the fanShow command to verify all the fans are working properly.
Make sure that the area is well-ventilated and that the room temperature is within operational
range of your switch. Refer to the hardware reference manual for your switch for the operational
temperature range.
If the message persists, replace the faulty blade.
Severity
CRITICAL
HIL-1504
Message
normal temperature specifications (
Probable Cause
Indicates that temperatures in the system have returned to normal.