PLAT-1000
Message
Probable Cause
Indicates nonrecoverable PCI errors have been detected.
Recommended
Action
The system will be faulted and might automatically reboot.
If the system does not reboot, then try issuing the reboot command from a command-line prompt.
Run the supportFtp command (as needed) to set up automatic FTP transfers; then run the
supportSave command and contact your switch service provider.
Severity
CRITICAL
PLAT-1001
Message
which CP (0 or 1) is doing the reset> resetting other CP (double reset may occur). Probable Cause Indicates the other CP is being reset. This message is typically generated by a CP that is in the Recommended Action No action is required. Severity INFO PLAT-1002 Message Contents are platform-specific> CP Error platform-specific>. Probable Cause Indicates that the CP cannot access the I2C subsystem either because of an error condtion or Recommended Action Reboot the CP if it does not reboot itself. Reseat the CP if rebooting does not solve the problem. If
process of becoming the active CP. Note that in certain circumstances a CP may experience a
double reset and reboot twice in a row. A CP can recover automatically even if it has rebooted twice.
being fenced or isolated from the I2C bus.
the problem still persists, then replace the CP.